997-492-000-5, Issue 5
June 2009
26
EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
7.2 Panel Options - A
Four user-configurable panel options are available:
a. Enable/Disable Engineering Mute
b. Enable/Disable Commissioning Mode
c. ACCEPT pushbutton access level
d. LAMP TEST pushbutton access level.
e. Delay Lights DISABLEMENT LED
7.2.1 Engineering Mute
The operation of the panel’s buzzer can be changed so that it
operates only occasionally with a Fire state, fault condition or
during any active configured first stage delays. This can be
selected independently of Commissioning Mode.
The default is Engineering Mute disabled.
7.2.2 Commissioning Mode
The panel can be put in Commissioning Mode to assist
the commissioning process.
In this mode, most faults are indicated after 4 secs instead
of the normal 20 secs delay to aid fault finding.
Commissioning Mode times-out automatically 60 secs after
the cover is replaced. Selection of commissioning Mode
automatically selects the Engineering Mute function.
7.2.3 ACCEPT Pushbutton Access Level
The ACCEPT pushbutton can be configured to operate at
access Level 1 or 2. The default operation is access Level 2.
7.2.4 LAMP TEST Access Level
The LAMP TEST pushbutton can be configured to operate at
access Level 1 or 2. The default operation is access Level 2.
7.2.5 Delay Lights DISABLEMENT LED
EN 54-2 and ISO 7240 Annex E acknowledges that delays
may be permanently configured in the normal mode of
operation of the equipment, (e.g. day mode) and in such
cases there is no need for a disablement indication. Use
this option when the DISABLEMENT LED is required to
indicate any configured delays.
7.3 Panel Options - B
The following options are selectable:
a. Non-latched faults
b. Pulse Fire Routing outputs
c. FBF Fire Routing disable - forces off
d. Re-sound - new zone in alarm
e. Mains fault delay.
7.3.1 Non-latched Faults
When enabled, this option allows faults and fault indications
to clear automatically. The buzzer can still be silenced while
a fault is shown on the panel (it will resound if the fault
reoccurs). By default the option is disabled and fault
indications require manual intervention to clear.
EN 54-2 & ISO 7240-2: Annex E
Does not require delay
indicated as a disablement.