1.5 EN 54 Functions
This fire control panel is designed to comply with the
requirements of EN 54 Part 2/4. In addition to the basic
requirements of EN 54-2, the panel may be configured to
conform with the following optional functions - the applicable
clauses of these standards are referenced as follows:
Options Clause
Indications:
Fault signal from fire protection equipment 7.10.4
Controls:
Delay to Outputs 7.11.1
Manual or automatic switching of delays to outputs 7.11.2
Dependency on more than one alarm signal, Type B 7.12.2
Test condition 10
Outputs:
Fire alarm device(s) 7.8
Fire alarm routing equipment 7.9.1
1
Fire alarm routing equipment with alarm confirmation 7.9.2
1
Automatic fire protection equipment: Type A 7.10.1
1
Automatic fire protection equipment: Type C 7.10.3
1
Fault warning routing equipment 8.9
1
Only available when using the optional 4-way sounder
PCB to allow monitoring of the transmission path.
1.6 ISO 7240 Functions
This fire control panel is designed to comply with the
requirements of ISO 7240 Part 2/4. In addition to the
basic requirements of ISO 7240-2, the panel may be
configured to conform with the following optional
functions - the applicable clauses of these standards
are referenced as follows:
Options Clause
Controls:
Delay to Outputs 7.11
Dependency on more than one alarm signal, Type B 7.12.2
Test condition 10
Outputs:
Fire alarm device(s) (Sounders) 7.8
Fire alarm routing equipment 7.9.1
1
Fire alarm routing equipment with alarm confirmation 7.9.2
1
Fault warning routing equipment 8.9
1
Only available when using the optional 4-way sounder
PCB to allow monitoring of the transmission path.