997-492-000-5, Issue 5
June 2009
34
EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
8 Specification
General
The Fire Control Panel meets the requirements of EN 54-2/
4 and ISO 7240-2/4. See Section 1.4 CE Marking for further
details.
Mechanical:
Construction: Fire-resistant, ABS plastic moulded front
cover and back box. Cover contains all
user interface controls and visual
indicators.
Dimensions (mm): 318(h) x 356(w) x 96(d)
Approx. Weight: 2kg (no batteries)
Environmental:
Climatic classification: 3K5, (IEC 721-2-3)
Operating temperature: -5
o
C to +45
o
C, (recommended +5
o
C to
35
o
C)
Humidity: 5% to 95% R.H.
Height above sea level:Maximum, 2000m
Panel sealing: IP 30, (EN 60529)
Vibration: EN 60068-2-6, 10-150Hz at 0.981ms
-2
,
0.1g
n
(Meets the requirements of
EN 54-2/4)
EMC: Emissions: EN 61000-6-3
Immunity: EN 50130-4
Safety: EN 60950
Indicators and Controls:
LED Status indicators:Alarm, Zonal Fire, Zonal Fault, Power,
General Fault, General Disablement, Test,
Delay On (active), System Fault, Earth
Fault, Power Supply Fault, Sounder Fault/
Disabled, Fire Routing Active, Fire
Routing OutputFault/Disabled, Fault
Output Fault/Disabled, Auxiliary Fault.
Controls:
Two-position keyswitch:
Level 1 (key removed or in ‘remove’ position)
Level 2 access (key turned 90° clockwise).
Dedicated push-buttons are provided for the following functions:
ACCEPT, SOUNDERS STOP/START,
RESET, BUZZER MUTE, DELAY ON/
OFF, ITEM SELECT, DISABLE/TEST/
NORMAL, LAMP TEST.
External Connections:
Cable entry: 18 x 20mm knock-outs on top face of
back box. One 25mm x 50mm knock-
out on rear wall of back box.