EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
by EN 54-13. A fault of the 4-way sounder PCB is indicated
by the Auxiliary fault indicator. The following output options
are configurable:
- Sounder output
- ÜE transmission circuit
- Fire protection output (SST)
- Fire routing output
- Fault routing output
The following input options are configurable:
- Fire transmission confirmed
- Fault transmission confirmed
- Class change
- Day Mode
Maximum ouput current (per PCB):
For two or more ouputs (if DIP switch 6 set to >250mA): 1.5A
For each output (if DIP switch 6 set to <250mA): 250mA
Digital Inputs: 2 x 32Vdc.
Digital Inputs:
0- 32Vdc or contact closure.
Low = 0 - 1.35Vdc
High = 3.15 - 32Vdc.