8
When configuring the use of Output Relays, configure them also as described for Output Relays in the manual for the SYSTEM.
To view the status of a connected tachometer, Click on the Sensor description or click on “View”
The status page for the sensor will open, displaying the default value of the sensor with a 0-255Hz range of sensing operation.
To configure the sensor for specific use, click on “Configure” to open a page with variable values (see image on next page).
Most of the sensor settings are the same as any other sensor configuration (detailed in the SYSTEM manual) but there are some
differences:
Sensor Settings Description
Associate Sensor Select if the Type “DIO” should be replaced by the sensor type to be entered in the next box.
Associated Sensor Type Enter the “Type” of sensor that should be displayed on the summary page and in all alert
communications received regarding this sensor
Associated Sensor Unit Enter between 1 and 3 alphabetical characters. (Ex. MPH for Miles Per Hour) These
characters will be used by the ENVIROMUX to represent the unit of measure reported by the
attached sensor. Leaving it empty will result in an empty string in the reported data. For
example, a value will be reported on the status page, but no unit of measure will be displayed.
SNMP Associated Type ID Enter ID value from MIB file if SNMP traps will be used for alert notifications for this sensor (for
more on this, see “SNMP Custom Type ID” on next page)
Min. Associated Level The minimum range of the units to be associated with the cycle count measured from the
attached sensor.
(Ex. the E-WSS associates one rotation within 1 second to be a wind speed of 2.5MPH. With
an maximum operating range of 255Hz (or cycles), the maximum wind speed measurement will
be 637.5MPH (255Hz X 2.5MPH).)
Max. Associated Level The maximum range of the units to be associated with the current reading measured from the
attached sensor.
SNMP Custom Type ID: Use this field if SNMP traps will be used for alert notifications. The Type ID corresponds with a value
defined in the MIB file under allExternalSensorsType” (default value is 32567 for type “Custom”). Place the desired number in
this box that represents the type of sensor to be reported in the MIB browser or SNMP trap.
Click here to open
confi
uration
a
e
o view status,
click either link