EasyManua.ls Logo

NTI TFTN285 - Page 50

NTI TFTN285
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Manual TFTN 085-199
50
Figure 10-5 Plumbing Schematic CH Zone Valves & Downstream IWH
NOTES:
1. For ZONE 1-3 to output 24VAC (like in this example), jumper ZONE INPUT to R (24V)
2. The BOILER PUMP is responsible for circulating water through the boiler, so size accordingly (see Table 10.3).
3. If using a System Sensor, set Sensor Configuration option Auxiliary Sensor 1 (24.6.1) = System Sensor.
4. If application uses a System Sensor, it will be necessary to set DHW Setup option DHW Mode = Downstream IWH (Tank Sensor
or Aquastat); otherwise it is acceptable to be set as Upstream IWH (Tank Sensor or Aquastat).
1
2
3
4

Other manuals for NTI TFTN285

Related product manuals