Trinity Lx Installation and Operation Instructions Lx Series
6
2.0 SPECIFICATIONS
Table 2-1 Specifications Lx150-300
DESCRIPTION Lx150 Lx150E Lx200 Lx300
CSA Input Modulation
1
btu/hr [kw]
30,000-150,000
2
[8.8-44.0]
30,000-150,000
[8.8-44.0]
40,000-199,000
[11.7-58.3]
55,000-275,000
[16.1-80.5]
DOE Heating Capacity
1, 3
btu/hr [kw]
136,000
[39.8]
139,000
[40.7]
182,000
[53.3]
251,000
[73.5]
Net I=B=R Rating
1,3
btu/hr [kw]
118,000
[34.8]
121,000
[35.4]
158,000
[46.3]
213,000
[62.4]
DOE AFUE
3
% 95.1 97.0 95.1 95.1
Recovery Rating @
100
o
F Rise, gal/hr
- - 224 310
Water Connections - NPT, in. 1
4
1 1 1-1/4
Gas Connection - NPT, in. 1/2 1/2 1/2 1/2
Vent/Air-Intake
Pipe
Dia.
respectively, in. [mm]
5
3
7
or 4
[ 76 or 102]
3
7
or 4
[ 76 or 102]
3
7
or 4
[ 76 or 102]
4 or 6
[102 or 152]
Vent/Air-Intake,
Max. Length, ft. [m]
105
7
[32]
105
7
[32]
105
7
[32]
100
[30.5]
Dimensions H x W x D
in. [mm]
29.5x17x18.5
[749x432x470]
29.5x17x18.5
[749x432x470]
29.5x17x18.5
[749x432x470]
36x17x21.5
[915x432x546]
Approx. Appliance Weight
with Water, lbs [kg]
100 [45.3] 125 [56.7] 125 [56.7] 180 [81.6]
Electrical Rating 120V / 1 Phase / 60 Hz / 12A
Table 2-2 Specifications Lx400-800
DESCRIPTION Lx400 Lx500 Lx600
6
Lx700
6
Lx800
6
CSA Input Modulation
1
btu/hr [kw]
75,000-399,000
[21.9-117]
100,000-500,000
[29.3-146]
120,000-600,000
[35.1-176]
160,000-700,000
[46.9-205]
160,000-800,000
[46.9-234]
Heating Capacity
1
btu/hr [kw]
374,000
[109.6]
468,000
[137]
562,000
[164]
655,000
[192]
749,000
[219.5]
Steady State Efficiency Rating
% 94.0 94.0 94.0 94.0 94.0
Recovery Rating @
100
o
F Rise, gal/hr
450 564 677 789 902
Water Connections - NPT, in. 1-1/4 2 2 2 2
Gas Connection - NPT, in. 3/4 3/4 1 1 1
Vent/Air-Intake
Pipe
Dia.
respectively, in. [mm]
5
4 or 6
[102 or 152]
4
9
or 6
[102 or 152]
4
9
or 6
[102 or 152]
4
8
or 6
[102 or 152]
4
8
or 6
[102 or 152]
Vent/Air-Intake,
Max. Length, ft. [m]
100
[30.5]
100
9
[30.5]
100
9
[30.5]
100
[30.5]
100
[30.5]
Dimensions H x W x D
in. [mm]
36x17x 24
[915x432x610]
43x17x 32.5
[1092x432x825]
37x17x 47.5
[938x432x1206]
37x17x 63.5
[938
x 432 x 1613]
37x17x
63.5
[938
x 432 x 1613]
Approx. Appliance Weight
with Water, lbs [kg]
225 [102] 320 [145] 380 [172] 425 [193] 475 [215]
Electrical Rating 120V / 1 Phase / 60 Hz / 12A
Notes for Tables 2-1 and 2-2:
1
Listed Input and Output ratings are at minimum vent lengths at Sea Level. Numbers will be lower with longer venting
and/or altitudes greater then 2000 feet [610 m].
2
The maximum output when operating on LP-Gas is limited to 145,000 Btu/hr [42.5 kW].
3
Based on rating plate input capacities, using standard test procedures prescribed by the U.S. Department of Energy.
Ratings have been confirmed by AHRI (GAMA), excluding Lx400 and Lx800.
4
Units sold in Canada are 3/4” NPT.
5
Trinity Lx require a special venting system, use only vent materials and methods detailed in these instructions.
6
Models Lx600, Lx700 and Lx800 operate with Natural Gas only.
7
Models Lx150-200, when using 3" venting on LP, max. equivalent length = 50 feet.
8
Only 6” exhaust vent is permissible for the Lx700 and Lx800. Air intake pipe can be 4” or 6”.
9
Models Lx500 and Lx600 are limited to 30’ of 4” or 90’ of 6”exhaust venting when using the Indoor Combustion Air Kit.

Related product manuals