Trinity Lx Installation and Operation Instructions Lx Series
70
Table 14-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Hold 66 – Interrupted air
switch ON (and blower is on)
- Blower problem
- Faulty controller
Check low voltage wiring from blower to
controller. Check VDC signal from red–green
and black-green; if not 28-32VDC and 0 VDC
respectfully – replace controller. If signal is
correct – replace blower.
Insufficient water pressure Ensure at least 15PSI at appliance outlet. Refer to
Supplementary Documentation section 2.0 System
Piping.
Hold 67 – ILK OFF
External Limit Tripped Indication that an external limit (wired to “LIM”)
is open. Not a problem with boiler, check
external limit.
CH or DHW settings Check if CH and/or DHW set point temperature
plus off hysteresis exceeds 210°F (99°C).
Hold 79 – Outlet High Limit
CH or DHW pump problem
See
"Inoperative CH or DHW pump" below.
Lockout 81 – Delta T limit
OR
Appliance making banging or
hissing sounds
Insufficient water flow
Check Fuse "A"
Check appliance pump.
Ensure plumbing is correct. Refer to
Supplementary Documentation section 2.0
System Piping. Check that water pressure is at
least 15PSI.
Boilers Only - Boiler heat transfer surfaces
may be fouled with scale or magnetite. Clean
with Fernox DS-40 Descaler and Cleanser. See
Table 2-1 in Appendix B.
Dirty heat exchanger Inspect and if required clean the combustion
chamber and/or heat exchanger. Refer to 14.0
Annual Manintenance and Inspection and
Supplementary Documentation section 2.0 System
Piping.
Lockout 82 – Stack limit
Faulty sensor Check resistance of stack sensor and compare to
thermistor resistance chart, see Table 14-2.
Lockout 85 – Inlet/Outlet
Inversion Limit
Pump flowing in the wrong
direction
Ensure water circulation is flowing into the boiler
at the fitting closest to the wall.
Lockout 88 – Outlet T Rise
limit
Insufficient water flow See Lockout 81.
Sensor disconnected
Verify that 2-position Molex connector on
wiring harness is securely attached to mating
connector on inlet sensor.
Inspect sensor wiring.
Hold 91– Inlet sensor fault
Faulty sensor Check resistance of sensor and compare to
thermistor resistance chart, see Table 14-2.
Sensor disconnected
Verify that 4-position Molex connector on
wiring harness is securely attached to mating
connector on outlet sensor.
Inspect sensor wiring.
Hold 92 – Outlet sensor fault
Faulty sensor Check resistance of sensor and compare to
thermistor resistance chart, see Table 14-2.
Sensor disconnected
Verify that 4-position Molex connector on
wiring harness is securely attached to mating
connector on stack sensor.
Inspect sensor wiring.
Hold 95 – Stack sensor fault
Faulty sensor Check resistance of sensor and compare to
thermistor resistance char
t
, see Table 14-2.