EasyManua.ls Logo

NTI Trinity Lx 150 - Page 9

NTI Trinity Lx 150
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lx Series Installation and Operation Instructions Trinity Lx
9
Figure 3-1(a) Lx150-200 Models
Closet Installation, Minimum Clearances
Figure 3-1(b) Lx300-400 Models
Closet Installation, Minimum Clearances
Closet/alcove installations in US and Canada require approved CPVC vent and air-inlet
pipe, fittings, cements and primers (Table 4-3).
Ventilation Air Openings
are not required if the
appliance area meets
the listed Recommended
Clearances in Table 3-1.
Top 12” [305 mm]
6” [152 mm] max. above vent opening
Front 6” [152 mm] - Boilers
Front 36” [915 mm] - Water Heaters
Left Side 12” [305 mm]
Right Side 12” [305 mm]
6” [152 mm] max. below vent opening
Ventilation Air Opening
1 in
2
per 1000 Btu/hr, min. 100 in
2
Ventilation Air Opening
1 in
2
per 1000 Btu/hr, min. 100 in
2
Removable Surface or Closet Door
Piping must be CPVC
1” [25 mm] clearance for
hot water and vent pipes
Ventilation Air Openings
are not required if the
appliance area meets
the listed Recommended
Clearances in Table 3-1.
Top 12” [305 mm]
Removable Surface or Closet Door
Ventilation Air Opening
1 in
2
per 1000 Btu/hr, min. 100 in
2
Ventilation Air Opening
1 in
2
per 1000 Btu/hr, min. 100 in
2
6” [152 mm] max. above vent opening
6” [152 mm] max. below vent opening
Right Side 4” [102 mm]
Left Side 12” [305 mm]
Front 6” [152 mm] - Boilers
Front 36” [915 mm] - Water Heaters
Piping must be CPVC
1” [25 mm] clearance for
hot water and vent pipes

Related product manuals