Trinity Lx │Installation and Operation Instructions Lx Series
Figure 3-1(c) Closet Installation, Minimum Clearances (Lx500-800)
Table 3-1 Minimum Clearances for Installation and Service
Notes:
1
6” if surface is removable allowing 24” clearance (i.e. closet installation). See Ventilation Air Opening dimensions in
Figure 3-1.
2
Clearances can be as low as 12” if the right side has a clearance of 24”.
3
For models Lx500-800, ensure rear of unit is accessible for wiring and flue gas testing.
6” [152 mm]
max. below
vent opening
1” [25 mm]
clearance for
hot water and
vent pipes
6” [152 mm]
max. above
vent opening
Removable Surface
or Closet Door
Ventilation Air Opening
1 in
2
per 1000 Btu/hr,
min. 100 in
2
Ventilation Air Opening
1 in
2
per 1000 Btu/hr,
min. 100 in
2
Ventilation Air Openings -
Openings are not required if
the appliance area meets the
Recommended Clearances in
Table 3-1.
Access - Ensure rear of unit is
accessible for wiring and flue
gas testing. See Table 3-1.