4002 non-addressable control and indicating equipment
User Manual
6
32-0015-r06_2018-03
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information shown were current at the date of publication and subject to change without notice.
3. CONDITIONS
3.1. Quiescent Condition
The Quiescent Condition is the normal condition for the control and indicating equipment. In the Quiescent
Condition, only the SUPPLY LED is on.
3.2. Alarm Condition
When the control and indicating equipment enters the Alarm Condition, the alarm sounders and output modules
will operate according to their configuration programming.
3.3. Actions During the Alarm Condition
3.3.1. Fire Investigation
After the control and indicating equipment enters the Alarm Condition, take the following actions.
1) Press ACKNOWLEDGE to acknowledge the Alarm and silence the internal sounder. The FIRE and
relevant detection zone LEDs will be on steady, and the internal sounder will silence.
2) Investigate the source of the Alarm condition.
3) If the building or area needs to be evacuated, once the area(s) is cleared, silence the alarm devices by
pressing the SILENCE/ACTIVATE ALARMS button. Alarm devices can be re-started by pressing the button
a second time.
4) If the cause of the Alarm Condition was not a fire, enter Access Level 2 and press the RESET button to
reset the fire detection and alarm system.
5) If the cause of the Alarm Condition has not cleared, the control and indicating equipment will re-enter the
Alarm condition. If this occurrence repeats, disable the zone and contact the service company.
The FIRE LED will
flash. The internal
sounder will
operate.
The ZONES FIRE LED
(
s
)
will flash.
The ACKNOWLEDGE
LED will flash.
The ACTIVATE/SILENCE
ALARMS LED will
illuminate.
INVESTIGATE THE SOURCE OF THE ALARM CONDITION.
IF A FIRE EXISTS INITIATE YOUR BUILDING EVACUATION PLAN.
DO NOT RESET THE CONTROL AND INDICATING EQUIPMENT UNTIL THE
SOURCE OF THE ALARM HAS BEEN DETERMINED.