EasyManua.ls Logo

Oceanic OCL - CDT Lead-in and Status; Set CDT Configuration; Set Free Alarms Menu

Oceanic OCL
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
OCL OPERATING MANUAL
© 2002 Design, 2014 Doc. No. 12-5378-r01 (4/9/15)
>> If On is saved and a CDT was set, the CDT will start counting down and operation will revert to the Lead-in.
>> If Off is saved, the Timer will stop counting down and operation will revert to the Lead-in.
>> If Set is saved, the Set CDT screen will be displayed.
• S (2 sec) - to revert to CDT Lead-in.
Set CDT, information includes (Fig. 107):
> Graphics SEt and CDT
> CDT (min:sec) with Minute digits ashing
> min and sec icons
• A (hold) - to scroll upward through Minute Set Points at a rate of 8 per second from 0: to 59: in increments of 1: (min).
• A (< 2 sec) - to step upward through Set Points one at a time.
• M (< 2 sec) - to step back through Set Points one at a time.
• S (< 2 sec) - to save the Minute Set Point and ash the Seconds digits.
• A (hold) - to scroll upward through Seconds Set Points at a rate of 8 per second from :00 to :59 in increments of :01
(sec).
• A (< 2 sec) - to step upward through Set Points one at a time.
• M (< 2 sec) - to step back through Set Points one at a time.
• S (< 2 sec) - to save the CDT min:sec setting and revert to the CDT Status screen with OFF ashing.
--------------------------------------------------------------------------------------------------------------
SET FA (FREE ALARMS) MENU
Sequence >> Lead-in >> EDT >> DA1 >> DA2 >> DA3
Set Points remain as set until changed.
Set FA Lead-in, information includes (Fig. 108):
> Graphics SEt and FA
• A (< 2 sec) - to step forward to Set M Lead-in.
• M (< 2 sec) - to step back to CDT Lead-in.
• S (< 2 sec) - to access Set EDT Alarm.
EDT (ELAPSED DIVE TIME) ALARM
Factory set for a xed 30 seconds, the EDT alarm sounds the audible every 30 seconds during FREE dives.
Set EDT Alarm, information includes (Fig. 109):
> Graphics SEt and EDT -
> OFF (or ON) ashing
• A or M (< 2 sec) - to toggle between ON and OFF.
• S (< 2 sec) - to save the setting and access Set DA1.
• S (2 sec) - to step back to Set FA Lead-in.
DA (DEPTH ALARMS)
There are 3 Free Depth Alarms (DAs) that can be set at progressively deeper depths*.
*The DA2 setting must be deeper than DA1 and DA3 must be deeper than DA2.
Set DA1 Alarm, information includes (Fig. 110A):
> Graphics SEt and - dA1
> Graphic OFF, or Depth value with MAX and FT (or M) icons, ashing
• A (hold) - to scroll upward through settings at a rate of 8 per second from OFF to 30 to 330 FT (10 to 100 M) in
increments of 10 FT (1 M).
• A (< 2 sec) - to step upward through settings one at a time.
• M (< 2 sec) - to step back through settings one at a time.
• S (< 2 sec) - to save the setting.
> If OFF is saved, operation reverts to Set FA Lead-in.
> If a Depth value is saved, Set DA 2 is accessed.
• S (2 sec) - to step back to Set EDT Alarm.
Set DA 2 and DA 3 are similar with Depth values beginning 1 increment higher (deeper) than the previous
selection set. Example: If DA 1 is set for 100 FT, DA 2 settings start at 110 FT.
If DA 1 (or DA 2) is set OFF, a Set DA 1 (or 2) First message will be displayed (Fig. 110B) when attempt is made to access Set
DA 2 (or 3).
Fig. 107 - SET CDT
Fig. 106B - CDT STATUS
(to access Set)
Fig. 108 - SET FA LEAD-IN
Fig. 109 - SET EDT ALARM
Fig. 110A - SET DA1
Fig. 110B - SET DA1
FIRST MESSAGE

Table of Contents

Related product manuals