Page 46
DIFFERENTIAL PRESSURE TRANSMITTER - USER GUIDE
11. HART DEVICE CONNECTION
1. HART Support
4-20 mA/HART (LCD and Non-LCD) models support HART Universal and
Common Practice Commands, which are compatible with most of the
HART field Communicators.
2. Steps to connect to the HART device
a. Connect the HART modem to the HART device.
b. Run the HART software.
c. Select Tools from the toolbar.
d. Select Default Params.
e. Select the serial port for the HART device.
f. Select the device’s polling address.
g. Set the display units.
h. Click update.
i. The device should be connected.
3. Steps to change the HART ID
a. Complete the steps above.
b. Once you have a stable connection, click on the instrument number.
c. On Station, change the value as needed.
d. Click update.
e. On the bottom left of the screen set the new ID number.