On entering function [78] the function display will read 78.
The upper display shows 30.00 mV setting.
Enter the exact mV as measured by the millivolt meter.
The main display will flash all zero’s. During this period the controller is
checking calibration so do not alter the mV reading. When the flashing
stops, the calibration is complete and the controller will return to
“RUN” Mode.
To increment the flashing digit press the button
To advance to the next digit press the button
To save the mV setting and start calibration press the button
37
Function [79] does not control any other function
On entering function [79] the function display shows 79.
The zone display shows blank.
The upper display shows 0.
By advancing the flashing digit the operator can select
[0] to return with no changes
[1] to [6] to start profile on any one zone 1 to 6
[7] to start profiles on all enabled zones 1 to 6
To increment the flashing digit press the button
To start profile and return to “RUN” mode press the button
6.12 Function [79] Start Profile
Standard Ranges [40 Mv]
TC ºC Range ºF Range
B 0-1800 32-3300
C 0-2300 32-4200
E 0-500 32-1000
J 0-750 32-1400
K 0-1000 32-1900
R 0-1750 32-3200
S 0-1750 32-3200
T 0-400 32-750
Extended Ranges [75 Mv]
E 0-1000 32-1800
K 0-1300 32-2500
Open Collector Transistor Diagram for Output
Microprocessor Bus
7.1 Thermocouple Ranges
38
5 VDC
DC Z1 Z2 Z3 Z4 C C Z5 Z5 Z6 Z6 Up to 40 VDC
External Power supply
Internal
Power
Supply
Note ! Extended range will work with all Standard range thermo-
couples, but it is better to use Standard range for thermocouples with
output below 40 Mv.
Note ! See page 40 for Wiring Diagram of controller outputs