EasyManua.ls Logo

Omega CN616TC1 - Page 24

Omega CN616TC1
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setup - Power the CN 616 controller
1. MODEL SELECTION.
To comply with the requirements, the following model must be
selected:
Standard control, Hi / Lo Alarm with Non Latching Relay, ºF.
Type “K” thermocouple
Looking on page 28 in the Manual the model will be coded as: 2 3 0 4.
2 - Hi / Lo Alarm
3 - Non latching relay, *F
0 - Standard control
4 - Type “K” thermocouple
Using procedure outlined on the inside back cover of this reference
card, load the above model number into the controller.
NOTE -
If Function 99 appears during setup- it means that the password
protection is enabled. Follow instructions on page 25 of the Manual to
enter the password. Password is factory preset at 1 0 1 1. It may be a
good idea to disable the Password protection at this time. Use proce-
dure on page 27 and load “0” in Function 32. If password protection is
desired, enable the password after the Controller setup is completed.
2. ZONE DISABLE - Page 27
Since only 4 zones are used, zones 5 & 6 should be disabled. Using
setup procedure outlined above set 31 within the Function 71 and
follow the zone enable procedure in the Manual on page 27.
3. ZONE DISPLAY TIME - Page 29
Using the setup procedure outlined above set 35 within Function 71
and follow the Zone display time instructions in the Manual on page 29.
4. SET SETPOINT - Page 29
Using setup procedure outlined on the inside back cover of this refer-
ence card, select Function 72 instead of 71. Select sub function 36
(Setpoint) and follow the procedure
43
On page 29 of the Manual to load the following setpoints :
Z1 - 400 º F
Z2 - 500 º F
Z3 - 530 º F
Z4 - 300 º F
Skip zones 5 & 6.
5. HIGH ALARMS - Page 30
Select Function 72 as above, select sub function 37 (Hi - Alarm).
Follow the procedure Outlined on page 30 in the Manual and set the
following alarms :
Z1 - 15 º F
Z2 - 15 º F
Z3 - 15 º F
Z4 - 20 º F
6. LOW ALARMS - Page 30
Select Function 72 as above, select sub function 38 ( Lo Alarm).
Follow the procedure Since only 4 zones are used, zones 5 & 6
should be disabled. Using setup procedure
Z1 - 20 º F
Z2 - 15 º F
Z3 - 20 º F
Z4 - 20 º F
7. PID CONTROL - Pages 31, 32, 33.
Even with the AUTOTUNE system certain parameters must be set
manually, these are :
CYCLE TIME - Minimum recommended 4 seconds
HYSTERESIS - Typical 1 º F
PID ZONES - Z1, Z2, Z3, Z4.
COOLING ZONES - None
Using the procedures outlined on pages 31, 32 & 33 of the manual,
load the above numbers.
44

Related product manuals