10
Input Fault Timer will not be recogniz ed (time = infinite).
SECURE MENU (cont'd)SECURE MENU (cont'd)
SECURE MENU (cont'd)SECURE MENU (cont'd)
SECURE MENU (cont'd)
SEnCSEnC
SEnCSEnC
SEnC Sensor Rate of Change: Select
OFFOFF
OFFOFF
OFF
,,
,,
,
1 1
1 1
1 to
4000 4000
4000 4000
4000 °F, °C , or counts per 1 second per iod.
This v alue is usually set to be slightly g reater than the f astest process response
expected during a 1 second per iod, b ut measured for at least 2 seconds. If the
process is f aster than this setting, the SEnC bAd error message will appear. The
outputs will then be tur ned off . This function can be used to detect a r unaw ay
condition, or speed up detection of an open ther mocouple. Use the
INDEXINDEX
INDEXINDEX
INDEX &
ENTERENTER
ENTERENTER
ENTER k e ys to reset.
SCALSCAL
SCALSCAL
SCAL Scale Low: Select
100100
100100
100 to
99999999
99999999
9999 counts below
SCAH.SCAH.
SCAH.SCAH.
SCAH. The total span betw een
SCAL SCAL
SCAL SCAL
SCAL
and
SCAH SCAH
SCAH SCAH
SCAH must be within 11998 counts. Maximum setting range is -1999 to +9999
counts. For Current and Voltage Inputs , this will set the lo w range end. V alue fix e d
for Ther mocouples and RTD ranges.
SCAHSCAH
SCAHSCAH
SCAH Scale High: Select
100100
100100
100 to
99999999
99999999
9999 counts above
SCAL SCAL
SCAL SCAL
SCAL. The total span between
SCAL SCAL
SCAL SCAL
SCAL
and
SCAH SCAH
SCAH SCAH
SCAH must be within 11998 counts. Maximum setting range is -1999 to +9999
counts. For Current and V oltage Inputs , this will set the high range end. V alue fix ed
for Ther mocouples and RTD ranges.
SPLSPL
SPLSPL
S P L Set Point Lo w: Select from
SCAL SCAL
SCAL SCAL
SCAL v alue to
SPH SPH
SPH SPH
SPH value . This will set the minim u m
SP1,SP2, ALLo, ALHi, SP1d, and SP2d values that can be entered. If an y of the
values are less than the SPL value, a chec k message will appear and the value will
not be accepted.
SPHSPH
SPHSPH
S P H Set Point High: Select from
SCAHSCAH
SCAHSCAH
SCAH v alue to
SPL SPL
SPL SPL
SPL v alue . This will set the maxim u m
SP1, SP2, ALLo, ALHi, SP1d, and SP2d values that can be entered. If an y of the
values are g reater than the SPH value , a check message will appear and the value
will not be accepted.
SP1oSP1o
SP1oSP1o
SP1o Set Point 1 Output Ter minal Assignment: Select
OutAOutA
OutAOutA
OutA or
Outb.Outb.
Outb.Outb.
Outb.
NONO
NONO
NO
TE:TE:
TE:TE:
TE: Reassigning the output ter minals does not change the Hardware type
assigned to those ter minals. For single set point models , SP1o is loc ked to OUT A.
OutAOutA
OutAOutA
OutA Set Point 1 output will be directed to ter minals 7 & 8 and Set Point 2 output
to ter minals 9 & 10.
OutbOutb
OutbOutb
Outb Set Point 1 output will be directed to ter minals 9 & 10 and Set Point 2 output
to ter minals 7 & 8.
S#OtS#Ot
S#OtS#Ot
S#Ot Set Point Output Type: Select
CYCY
CYCY
CY
,,
,,
,
OnOF OnOF
OnOF OnOF
OnOF
,,
,,
,
PUL PUL
PUL PUL
PUL, or
Ft Ft
Ft Ft
Ft. Fix ed for Current and Voltage ,
the Hardware Configuration has selected this .
CYCY
CYCY
C Y Cycle Rate, Adjustable Time Propor tioning.
CY#CY#
CY#CY#
C Y # Cycle Rate Time: Select
2 2
2 2
2 to
80 80
80 80
80 seconds.
OnOFOnOF
OnOFOnOF
OnOF On/Off Output.
SP#dSP#d
SP#dSP#d
SP#d Set Point Diff erential in 1 deg ree or count steps from 2 deg rees or
counts to full scale , b ut limited b y SPL and SPH.
PULPUL
PULPUL
P U L Pulse Time Propor tioning.
PUL#PUL#
PUL#PUL#
PUL# Pulse Width V alue: Select
11
11
1 to
7 7
7 7
7.
FtFt
FtFt
FtFast Time Propor tioning: Fixed at 1 second Time Base.
VV
VV
V
oltolt
oltolt
olt Propor tional Voltage , 0 to10 V.
CurrCurr
CurrCurr
Curr Propor tional Current, 0 to 20 mA.
S#StS#St
S#StS#St
S#St Set Point State: Select
dir dir
dir dir
dir or
rErE
rErE
rE.
dirdir
dirdir
dir Direct Action. As the input increases the output will increase . Most com-
monly used in cooling processes.
rErE
rErE
rE R everse Action. As the input increases the output will decrease. Most
commonly used in heating processes.
S#OLS#OL
S#OLS#OL
S#OL Set Point Output Lo w Limit: Select
0 0
0 0
0 to
90 90
90 90
90 % b ut less than
S#OH S#OH
S#OH S#OH
S#OH. This item limits the
lo w est output v alue . This is useful f or adding a bias to the process when needed.
When a current or voltage output is used, the standard output v alue is 0 to 20mA
or 0 to 10V. If 4 to 20 mA or 2 to 10 V is required, the S#OL value should be set for
20% to r aise the lo w est output.
S#OHS#OH
S#OHS#OH
S#OH Set Point Output High Limit: Select
1010
1010
10 to
102102
102102
102 % b ut g reater than
S#OLS#OL
S#OLS#OL
S#OL. This item