9-19
Meter Function Menus
9
* The ‘MIN’ button allows you to sequence through SPC.1, SPC.2,
SPC.3, SPC.4, SPC.5, SPC.6, SPC.7 and SPC.8.
The ‘MAX’ button allows you to select the “0” or “1” state for each “SPC”
condition.
The ‘MENU’ button stores the selected values for each “SPC” condition
changed and advances the meter to the next configuration (“AL CNF”).
Every underlined “0” or “1” is the factory preset value.
9.2.11 AL CNF (Alarm Configuration)
Refer to Section 10 for an in-depth discussion of these features.
Alarm configuration is used to select:
the active zone for each alarm point to above or below the
setting [ALC.1 & ALC.4]
whether the open-collector output is on or off [ALC.2 & ALC.5]
whether the readings compared with the alarm points are filtered or
unfiltered [ALC.3 & ALC.6]
enabled or disabled alarm points [ALC.7]
MENU MIN/MAX/MENU *
BUTTON BUTTON
MAIN MENU SUB MENU DESCRIPTION
“AL CNF”: ALARMS 1 & 2 (SETPOINTS 3 & 4)
CONFIGURATIONS
Alarm 1 Active zone (Setpoint 3):
“ALC.1=0” Above
“ALC.1=1” Below
Alarm 1 open-collector or relay output
Active ON or OFF:
“ALC.2=0 On
“ALC.2=1” Off
Filtered/unfiltered reading compared
with Alarm 1 (Setpoint 3) value:
“ALC.3=0” Unfiltered
“ALC.3=1
Filtered
Alarm 2 Active zone
(Setpoint 4):
“ALC.4=0
Above
“ALC.4=1” Below
continued next page