EasyManua.ls Logo

Omega VSHP SERIES - Figure 19: Perimeter Panel Cabinet Base Height Calculation

Omega VSHP SERIES
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OMEGA-VSHP.F-IOM-1907
www.omega-heatpump.com 30
Perimeter Panel Cabinet Base Height Calculation
BH = Baseboard Height + Finish Floor Height*
G = Gap (min 0.5”)
B = Cabinet Base Height
(Min 5", increases in 1" increments)
B = BH + G + 0.5”
Note: *Include flooring thickness, underlayment, and any
concrete leveling as part of calculation.
Example:
If using a 5" baseboard, with 1” Finished Flooring height,
and 0.5" gap:
B = (5” + 1”) + (0.5”) + 0.5”
B = 7"
Therefore a 7” Cabinet Base is required.
G
BH
B
0.5"
Flooring
Cabinet
Base
Concrete
Slab
Baseboard
Perimeter
Return Air
Panel
Example: Baseboard to Base Height Table
Baseboard Height* Cabinet Base Height
Up to 3" 5"
>3" to 4" 6"
>4" to 5" 7"
>5" to 6" 8"
*Includes 1" Total Flooring
*Using gap G= 0.5" (from top of baseboard to
return panel flange)
Figure 19 Perimeter Panel Cabinet Base Height Diagram