OMEGA | WATER SOURCE HEAT PUMPS                                                                 OMEGA-VSHP.F-IOM-1907 
 
 
5  www.omega-heatpump.com   
 
 
 
3. GENERAL UNIT INFORMATION 
BLOWER & MOTOR 
The unit comes with a blower and motor assembly that 
is mounted to a blower deck inside the unit cabinet, lo-
cated above the chassis behind the electrical box. Re-
moval of the blower/motor assembly is done through the 
chassis compartment opening. 
UNIT NAMEPLATES 
The nameplate contains information about the unit in-
cluding model and serial numbers, electrical data and 
refrigerant charge information. The cabinet nameplate is 
located on the surface of the cabinet and the chassis 
nameplate is located on the chassis.  Collecting the in-
formation on the nameplate will be useful when contact-
ing your local customer service representative or when 
ordering parts. The compressor nameplate is located 
inside the chassis enclosure (requires removal of sheet 
metal enclosure) on the compressor shell.  
CONTROLS 
The unit comes with a factory supplied transformer. See 
wiring diagram for field wiring a thermostat to the electri-
cal box low voltage terminals. High voltage connection is 
made on the left side of the cabinet and low voltage con-
nections enter through the right side of the cabinet. 
MICROPROCESSOR CONTROLLER 
Unit comes with an advanced microprocessor controller 
that monitors the entire function of the unit. The micro-
processor board comes with an integral terminal strip for 
wiring thermostat cable.  
REFRIGERANT CONNECTIONS 
Low and high pressure side refrigeration service ports re 
located inside the compressor enclosure. Slide out chas-
sis and remove sheet metal enclosure to access fittings. 
CABINET– SILVER SERIES 
The standard Silver series cabinet is a fully factory as-
sembled one piece cabinet. See Figure 1. Use flexible 
duct connections for connecting cabinet to supply ducts 
to prevent vibration and noise transmission into occu-
pant space. 
CABINET– OPTIONAL GOLD SERIES 
The optional Gold series cabinet comes in two sections 
for enhanced acoustic performance. See Figure 2. The 
upper section discharge plenum is lined with 1” thick 
insulation on all inside surfaces. Plenum is secured to 
cabinet with shipping brackets. Once discharge plenum 
is fastened to the underside of the concrete slab ship-
ping brackets must be removed. See Figure 4  for com-
parison of Silver and Gold series cabinets.  Factory in-
stalled flexible connection joins the upper and lower sec-
tions. “S” and “D” cleats are used to join upper and lower 
plenums to the metal portion of the flex connection. The 
plenum comes with factory pre-punched knockouts on 
all sides.  
RETURN AIR PANEL—ACOUSTIC & PERIMETER 
The Acoustic Return Air Panel is insulated with 1/2” 
thick, acoustic insulation and removable without tools to 
allow access to the filter and (optional) service discon-
nect switch. The panel is removed by swinging out and 
lifting it off the support pegs.  The panel should be flush 
mounted to the drywall after the cabinet and riser instal-
lation is complete. See Figures 14 to 17 for more de-
tailed information. 
The Perimeter Return Air Panel door is mounted in the 
drywall opening and fastened to the wall studs. See Fig-
ures 18 to 21 for more detailed information. 
Cabinet base height and maximum base-
board height dimensions can be determined 
by referencing Figures 16 & 20. Use appro-
priate Figure based on R/A Panel type or-
dered. 
THERMOSTAT 
Unit comes standard with a factory provided 24 inch 
long, 6-wire thermostat cable whip pre-wired to the con-
trol board terminal blocks. 
4. INSPECTION & STORAGE 
INSPECTION OF UNIT 
Prior to the installation of the unit perform the following 
checks: 
•  Visually inspect the packaging, cabinet and chassis 
for signs of shipping damage prior to signing the bill 
of lading. Check that the units match the sales order 
by referring to the cabinet and chassis nameplate 
information. 
•  Inspect the riser ends for any sign of damage. 
•  Verify breaker and power supply meet electrical 
nameplate requirements of the unit.  
•  Check that the nameplate of the units matches the 
floor plan layout. 
When construction is not complete including concrete 
core drilling, drywalling, plastering, painting or any work 
that would contaminate the storage space all necessary 
precautions are to be taken to prevent the cabinet and 
chassis from becoming contaminated.  Particulate infil-
tration (i.e. drywall dust) into cabinet and chassis coil 
could result in equipment damage.  Fumes could result 
in premature corrosion (formicary corrosion) of the chas-
sis air-coil resulting in refrigeration system leaks.