OMEGA-VSHP.F-IOM-1907 
www.omega-heatpump.com   6 
 
 
 
 
STORAGE 
Both cabinet and chassis units are designed for indoor 
use only.  Care must be taken to protect the unit from 
environmental damage. Store the chassis in an environ-
ment with a temperature above (32
o
F). To prevent con-
tamination the units should be stored indoors. For out-
door storage ensure: 
•  Units should be placed in an area that will not be 
exposed to moisture damage. Units should be 
placed on a dry surface and on a raised surface. Do 
not stack units.  
•  Cover the units with a waterproof tarp. 
•  Failure to keep the units dry could result in the inte-
rior insulation becoming wet and cause the growth 
of mold which is known to cause odors and serious 
indoor air quality problems and health issues. 
•  Chassis units must be stored in the upright position 
to keep oil in the compressor.  
•  Riser ends should be capped if being stored on site 
to prevent contamination from foreign objects and 
debris. 
Wet insulation can cause the growth of mould. 
Any sign of mould growth in the interior insula-
tion should be removed, cabinet interior disin-
fected  with  anti-microbial  cleaner  and  re-
placed prior to operating the unit. 
Do not store cabinets on their side when chas-
sis  units  are  inside.  Chassis  units  should  al-
ways be  stored  and  transported in the upright 
position  otherwise  damage  to  chassis  may 
occur. 
The  refrigeration  system  of  these  units  con-
tains  POE  oil.  PVC/CPVC  piping  is  prone  to 
failure  when  in  contact  with  POE  oil.  PVC/
CPVC  piping  should  not  be  used  for  water 
supply  and  return  with  any  heat  pump  prod  
ucts as this may result  in  failure of the system 
and serious property damage. 
Do not rest or lean the unit on the risers. Do not use 
the risers or stub-outs to pick up the unit. Only des-
ignated lift points should be used when moving or 
lifting cabinets. Do not drop the risers. 
 
5. CABINET & RISER INSTALLATION 
Risers are designed to have slight adjustments 
for riser system expansion and aligning the 
stub-outs in the cabinet opening.  When in-
stalling risers, do not let riser stubs bottom out 
in the riser swage.  
 
Risers are designed to allow for 1-1/2 inches of 
movement due expansion and contraction. If 
the total calculated riser expansion exceeds ±1
-1/2 inches the field must provide expansion 
compensators. 
 
Riser stub-outs should be located as centrally 
as possible in the cabinet opening. Do not al-
low stub-outs to rest or contact the sheet metal 
opening. 
 
Do not allow the risers to bottom out when 
installing into the swage. 
 
FOR SHIPPED LOOSE RISER SHUT-OFF VALVES 
Visually inspect riser stub-outs and shut-off 
valves for debris or damage. 
 
 
Follow industry standard soldering practices 
when soldering shut-off valves to riser stub-
outs.  
 
Ensure riser stub-out surface is cleaned of any 
residue, soot or oils. Failure to adequately 
clean soldering surfaces can result in water 
leaks, property damage and physical injury. 
 
When soldering shut-off valves to riser stub 
outs, adequately protect cabinet, insulation 
and any other equipment from exposure to 
flames and heat. 
 
CABINET INSTALL 
1. When cabinets are shipped with risers attached, place 
cabinets in a horizontal position on the floor (do not rest 
cabinet on the risers). 
2. If required, install any field or factory supplied riser 
extensions to the unit mounted risers. 
3. Raise the entire cabinet slowly upright while at the 
same time lowering the risers through the floor cut-out 
opening. Align the risers to the matching swaged section 
of the riser on the floor below.