OMNI 4000/7000 Installation Guide Rev H
Page A-4
Jumper Settings
A.3.1 A Module Process Input Type Analog
To configure an A module for Analog Inputs, set the jumpers according to these instructions.
Configure Inputs 1 and 2 for one of three analog signal types:
For 1-5 VDC Input, remove both RTD and 4-20 jumpers.
For 4-20 mA Input, install the 4-20 jumper.
For RTD Input, install the RTD jumper.
Configure Input 3 for one of the two analog signal types:
Install all four “A” jumpers.
For 1-5 VDC Input, remove the 4-20 jumper.
For 4-20 mA Input, install the 4-20 jumper.
Configure Input 4 for one of the two analog signal types:
Install all four “A” jumpers.
Install the DC coupling jumper.
Install the HI signal threshold.
For 1-5 VDC Input, remove the 4-20 jumper.
For 4-20 mA Input, install the 4-20 jumper.
Refer to Figure A-2 for default input and output jumper settings: Inputs Ch1 = 4-20mA,
Ch2 = 4-20mA, Ch3 = 4-20mA, Ch4 = 4-20mA and Output Ch2 = 4-20mA.
Figure A-2: A Module Analog Jumper Settings
INPUT 1INPUT 2INPUT 3INPUT 4
A
P
A
A
A
P
4-20
4-20
RTD
4-20
RTD
INPUT 2
INPUT 1
INPUT 3
HI
INPUT 4
THRESHOLD
AC
DC
AC
D/A2RTD2
SELECT EITHER:
CHANNELS 1 AND 2:
4-20
RTD
JUMPER
1-5vDC
4-20mA
RTD
INPUT
TYPE
SELECT INPUT TYPE
ANALOG OUT #2 = D/A2
RTD EXCITATION #2 = RTD2
'DC' JUMPER
INSTALL
OUTPUT #2
A
P
A
A
A
P
4-20
INPUT 4