ZEN V2 Units
11
Output Specifications (CPU Units and Expansion I/O Units)
Units with Relay Outputs
Units with Transistor Outputs
Item Specifications Circuit drawing
Maximum switching capacity 250 VAC/8 A (resistive load: cosφ = 1)
24 VDC/5 A (resistive load)
Use the following values for the total of all outputs.
CPU Units with 10 I/O points: 20 A max.
(15 A max. for Communications-type CPU Units)
CPU Units with 20 I/O points: 40 A max.
Expansion I/O Units: 20 A max.
Minimum switching capacity 5 VDC/10 mA (resistive load)
(failure level: P, reference value)
Relay life Electrical Resistive load: 50,000 times (cosφ = 1)
Inductive load: 50,000 times (cosφ = 0.4)
Mechanical 10 million times
ON response time 15 ms max.
OFF response time 5 ms max.
Item Specifications Circuit drawing
Maximum switching capacity 24 VDC +20%, 500 mA Each circuit is configured with an independent common
circuit
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
ON response time 1 ms max.
OFF response time 1 ms max.
Q0 to Q3/OUT0 to OUT3
Q4/Q6
COM
Q5/Q7
Models with
20 I/O points
only
L
L
L
Internal
circuit
1,000
300
100
10
02 4 6 8 10
Contact current (A)
30
50
500
250-VAC resistive load
24-VDC resistive load/
250-VAC inductive load
24-VDC inductive load
(t = 7 ms)
Life (× 10
3
)
The life under the worst conditions, of the output contacts used in
ZEN relay outputs is given in the above table. Guidelines for the
normal life of the relays are shown in the diagram on the right.
Life-test Curve (Reference Value)
Usage: 360 times/hour
Note: The switching capacity, switching durability, and applicable
load area when actually using the relay depend on the type of
load, environmental conditions, and switching conditions.
Therefore, be sure to confirm these conditions for the actual
machine before use.
Q0 to Q3/OUT0 to OUT3
Models with
20 I/O points
only
390 Ω
COM
Q4/Q6
Q5/Q7
28.8 VDC max.
28.8 VDC max.
L
L
L
L
1 kΩ
+
Internal
circuit

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CP2E and is the answer not in the manual?

Omron CP2E Specifications

General IconGeneral
Expansion I/O UnitsUp to 7 units
ModelCP2E
TypeProgrammable Logic Controller (PLC)
Analog InputsAvailable via expansion units
Analog OutputsAvailable via expansion units
Communication PortsRS-232C
Ethernet PortYes
Power Supply100 to 240 VAC or 24 VDC (depending on the model)

Related product manuals