EasyManua.ls Logo

Omron CS CJ1W-ETN21

Omron CS CJ1W-ETN21
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
Remote Mail Command Details Section 3-4
UMBackup (User Memory Backup)
Function Backs up (saves) the CPU Unit's user program in the CPU Unit's EM file
memory or a Memory Card mounted in the CPU Unit.
Command Format Details
Response Format
Subject: UMBackup
Notation Description Omission
Body: Para1:Destination folder
name
Example)
Specifying subdirectory OMRON in
the Memory Card:
Para1:MEMCARD\OMRON
Specifies the destination folder in
which the user program will be
saved.
MEMCARD specifies the Memory
Card's root directory.
EM specifies the EM file memory's
root directory.
Note If this parameter is omitted,
the default destination is the
Memory Card's root directory.
Can be omitted.
Para2:File name
Example)
Specifying USER.OBJ:
Para2:USER.OBJ
Specifies the name of the file in
which the user program data will be
saved.
Note If this parameter is omitted,
the default file name is
AUTOEXEC.OBJ.
Can be omitted.
Para3:Overwrite=OK or NG
Example)
Allowing existing file to be overwrit-
ten:
Para3:Overwrite=OK
Specifies whether or not an existing
file may be overwritten.
To allow an existing file with the
same filename to be overwritten,
enter "Overwrite=OK".
To prevent an existing file with the
same filename from being overwrit-
ten, enter "Overwrite=NG".
Note If this parameter is omitted,
overwriting is prohibited.
Can be omitted.
Attached file: None
Subject: Re:UMBackup
Response contents Description
Body: Response Code:@@@@ Refer to 3-4-2 Response List.
Response Status:@@@@ Refer to 3-4-2 Response List.
> Para1:Destination folder name Included only if this parameter was specified.
> Para2:File name Included only if this parameter was specified.
> Para3:Overwrite=OK or NG Included only if this parameter was specified.
Attached file: None

Table of Contents

Related product manuals