Appendix BSpecifications
126
Transistor Output Units
Item 3G2A5-OD411 3G2A5-OD412
Max. Switching
Capacity
12 to 48 VDC
+10%
/
–15%
, 1 A
(but, 4 A/common, 5 A/Unit)
12 to 48 VDC
+10%
/
–15%
, 0.3 A
(but, 4.8 A/Unit)
Leakage Current 0.1 mA max. 0.1 mA max.
Residual Voltage 1.4 V max. 1.5 V max.
ON Delay 0.2 ms max. 0.2 ms max.
OFF Delay 0.3 ms max. 0.3 ms max.
No. of Outputs 16 (16 outputs/common, 1 circuit) 32 (32 outputs/common, 1 circuit)
Internal Current
Consumption
160 mA, 5 VDC max. 230 mA, 5 VDC max.
Fuse Capacity 5 A, 250 V (two fuses) 1 per circuit, 1 total
(Cannot be changed by user.)
Power for
External Supply
50 mA, 12 to 48 VDC 10% min. 80 mA, 12 to 48 VDC 10% min.
Weight 500 grams max. 530 grams max.
Circuit
Configuration
Fuse/fuse
blowout de-
tection
Internal
Circuit
Internal
Circuit
OUT
00
OUT 07
COM
OUT 15
OUT 15
(0 V)
to
to
COM
(0 V)
12 to 48
VDC
OUT 08
+ V
*
*
Fuse/fuse blowout detection circuit
Internal
Circuit
Internal
Circuit
OUT 00
OUT 07
COM
OUT 08
OUT 15
(0 V)
to
to
12 to 48
VDC
COM (0 V)
OUT 00
OUT 07
COM (0 V)
OUT 15
OUT 08
COM (0 V)
to
I
II
to
Fuse
Terminal
Connections
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
15
COM (0 V)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
+
19
COM (0 V)
12 to 48 VDC
NC
12
to 48
VDC
Note:
Be sure to
supply power to
B18; otherwise cur
-
rent will leak
through the load
while the output is
OFF.
Because the com
-
mons are short-cir
-
cuited internally
,
they cannot be
used separately
and must be wired
according to the
diagram.
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
2
3
4
5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
0
1
6
7
8
9
10
11
12
13
14
15
COM(0
V)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
AB
II
I
+
COM(0 V)
COM(0 V)
COM(0 V)
12 to 48 VDC
12
to 48
VDC
NC
Note:
Be sure to
supply power to
B18; otherwise
current will leak
through the load
while the output
is OFF.
Because the
commons are
short-circuited
internally
, they
cannot be used
separately and
must be wired
according to the
diagram.
Dimensions A-shape B-shape