Com Data
for Modbus
SECTION 6 Communications Data for Modbus
6-12
Note: Not displayed on the Controller display when Alarm 3 is not assigned to the output.
Address
Parameter name Setting (monitor) value Level
Four-
byte
mode
Two-
byte
mode
0F22 2F11 Alarm 1 ON delay H'00000000 to H'000003E7 (0 to 999) Advanced
function
setting
0F24 2F12 Alarm 2 ON delay H'00000000 to H'000003E7 (0 to 999)
0F26 2F13 Alarm 3 ON delay (See
note.)
H'00000000 to H'000003E7 (0 to 999)
0F2A 2F15 Alarm 1 OFF delay H'00000000 to H'000003E7 (0 to 999)
0F2C 2F16 Alarm 2 OFF delay H'00000000 to H'000003E7 (0 to 999)
0F2E 2F17 Alarm 3 OFF delay
(See note.)
H'00000000 to H'000003E7 (0 to 999)
1000 3000 PV/SP Display Screen
Selection
H'00000000 (0): PV/SP
H'00000001 (1): PV/SP/multi-SP
PV/SP/MV
H'00000002 (2): PV/SP/MV
PV/SP/multi-SP
H'00000003 (3): PV/SP/multi-SP
H'00000004 (4): PV/SP/MV
H'00000005 (5): PV/SP/multi-SP
PV/SP/soak time remain
H'00000006 (6): PV/SP/MV
PV/SP/soak time remain
H'00000007 (7): PV/SP/soak time remain
1002 3001 MV Display Selection H'00000000 (0): MV (heating)
H'00000001 (1): MV (cooling)