Com Data for
CompoWay/F
3.1 Variable Area (Setting Range) List
3-7
Note: The alarm function can also be used in Controllers without alarm output terminals. In this case,
confirm alarm occurrences via the status data.
Note 1: Not displayed on the Controller display when Alarm 3 is not assigned to the output.
Note 2: After communications parameters have been changed, reset the Controller to enable them.
Varia-
ble type
Ad-
dress
Parameter name Setting (monitor) value Level
C3 (83) 000D Alarm 1 Type H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm with standby
sequence
H'00000006 (6): Upper-limit alarm with standby sequence
H'00000007 (7): Lower-limit alarm with standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11): Absolute-value lower-limit alarm with
standby sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
Initial set-
ting
C3 (83) 000E Alarm 2 Type H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm with standby
sequence
H'00000006 (6): Upper-limit alarm with standby sequence
H'00000007 (7): Lower-limit alarm with standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11): Absolute-value lower-limit alarm with
standby sequence
H'0000000C (12): No alarm function
H'0000000D (13): PV change rate alarm
C3 (83) 000F Alarm 3 Type (See note 1.) Same settings as the alarm 2 type
C3 (83) 0010 Communications Unit No.
(See note 2.)
H'00000000 to H'00000063 (0 to 99) Communi-
cations
setting
C3 (83) 0011 Communications Baud
Rate (See note 2.)
H'00000000 (0): 1.2
H'00000001 (1): 2.4
H'00000002 (2): 4.8
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
C3 (83) 0012 Communications Data
Length (See note 2.)
H'00000007 (7): 7
H'00000008 (8): 8
C3 (83) 0013 Communications Stop Bits
(See note 2.)
H'00000001 (1): 1
H'00000002 (2): 2
C3 (83) 0014 Communications Parity
(See note 2.)
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
C3 (83) 0015 Number of Multi-SP Uses H'00000000 (0): No multi-SP
H'00000001 (1): 2SP
H'00000002 (2): 4SP
Initial set-
ting

Table of Contents

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals