E5CC-800/E5CC-B-800/E5CC-U-800
10
External Connections
E5CC-800 (Screw Terminal Blocks)
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
5. Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring). Use a UL
category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring (internal wiring).
The E5CC-800 is set for a K-type thermocouple (input type = 5) by
default. An input error (UGTT) will occur if the input type setting does
not agree with the temperature sensor. Check the input type.
Control output 1
Relay output
250 VAC, 3A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
Relay outputs
Models with 2 auxiliary
outputs: 250 VAC, 3 A
(resistive load)
17
18 12
15
16
1
2
13
14
3
11
4
6
7
8
9
10
5
6
4
5
6
5
6
Pt
A
B
B
+
-
m
A
-
+
5
4
V
-
5
V
6
+
4
TC
4
I
(no polarity)
11
12
11
12
100 to 240 VAC 24 VAC/VDC
Auxiliary outputs 1, 2
7
8
9
10
Auxiliary output 2
Auxiliary output 1
804
Communications (RS-485),
and Event Inputs 3 and 4
801
Event Inputs 1
and 2, and CT1
802
Communications (RS-485),
CT1
B(+)
A(-)
RS-485
(2) Auxiliary Outputs
(3) Input Power Supply
(5) Sensor (Temperature/Analog) Input
(6) Options
+
-
3
1
2
3
1
2
-
Models with
1 Linear
Current Output
Models with
1 Relay
Output
3
(1) Control outputs 1, 2
OUT1
C
OUT1
Q
OUT1
R
1
2
Models with 1
Voltage Output
(for Driving SSR)
+
RX QX CX
Auxiliary outputs 1, 2
E5CC-@@ 2 @ S M - 8@@
(1) (2) (3) (4) (5) (6)
Terminal type
Use no-voltage inputs for the event inputs.
The polarity for non-contact inputs is given in parentheses.
13
14
15
16
17
18
13
14
15
16
17
18
EV1
EV2
CT1
(-)
CT1
16
17
18
13
14
15
EV3
EV4
B(+)
A(-)
RS-485
(-)