EasyManuals Logo

Omron E5CJ-Q2 User Manual

Omron E5CJ-Q2
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
25
p Proportional Band Setting It is possible to set the proportional band within a range of 0.1 to 999.9°C/°F.
i Integral Time Setting It is possible to set the integral time within a range of 0 to 3999 s.
d Derivative Time Setting It is possible to set the derivative time within a range of 0 to 3999 s.
It is possible to set the necessary output value when the E5J is in constant op-
eration within a range of 0.0% to 100.0%. The E5J will be balanced with a devi-
ation between the set point and process value in P or PD control mode. This
deviation is called offset. The offset can be removed by changing the manual
reset value.
ofr Manual Reset Value
Setting
Parameters on Display Level 1
Section 3-5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CJ-Q2 and is the answer not in the manual?

Omron E5CJ-Q2 Specifications

General IconGeneral
BrandOmron
ModelE5CJ-Q2
CategoryTemperature Controller
LanguageEnglish

Related product manuals