CompoWay/F
SECTION 2 CompoWay/F Communications Procedures
2-14
Error Occurred
Note: For details on AT (auto-tuning), refer to the separate User’s
Manuals.
Response code Error name Cause
1002 Command too
short
The command is too short.
1101 Area type error The variable type is wrong.
1100 Parameter error Bit position is not “00.
The write data is out of the setting
range.
3003 Read-only error Variable type “C0” was written to.
2203 Operation error The Communications Writing
parameter is set to “OFF” (dis-
abled).
Attempted to write to a parameter
in setup area 1 from setup area 0.
Attempted to write to a protect
parameter from other than the pro-
tect level.
AT (auto-tuning) was in progress.
(See note.)
EEPROM error