6 - 55
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-7 Initial Setting Level
6
tr-h
Transfer Output Upper Limit
There must be a transfer output.
The transfer output type must not be set to OFF.
tr-l
Transfer Output Lower Limit
• This parameter sets the upper and lower limit values of transfer outputs.
*1 The remote SP will be output while the SP Mode parameter is set to the Remote SP Mode.
*2 This function can be set for a Position-proportional Model, but the setting will be disabled.
*3 This function can be set for standard control or for a Position-proportional Model, but the setting
will be disabled.
*4 This setting is displayed only for a Position-proportional Model.
Related Parameter
Transfer Output Type (Initial Setting Level): Page 6-54
Transfer
output type
Setting range
Default
Unit
Transfer
output lower
limit
Transfer
output upper
limit
Set point
*1
SP lower limit to SP upper limit SP lower limit SP upper limit EU
Set point
during SP
ramp
SP lower limit to SP upper limit
PV Temperature
input
Input setting range
lower limit to input
setting range upper
limit
Input setting
range lower limit
Input setting
range upper
limit
Analog input Analog scaling
lower limit to analog
scaling upper limit
Scaling lower
limit
Scaling upper
limit
MV
(heating)
*2
Standard −5.0 to 105.0 0.0 100.0 %
Heating/
cooling
0.0 to 105.0
MV
(cooling)
*3
Valve
opening
*4
Position-
proportional
control
−10.0 to 110.0