A Appendices
A - 18
E5@C Digital Temperature Controllers User’s Manual (H174)
Meaning
“----” will be displayed for the Valve Opening Monitor parameter if any of the following error occurs.
Motor calibration has not been performed.
The wiring of the potentiometer is incorrect or broken.
The potentiometer input value is incorrect (e.g., the input is out of range or the potentiometer has
failed).
Action
Check for the above errors.
Operation
Close control: The control output is OFF or the value that is set for the MV at PV Error parameter is
output.
Floating control: Operation will be normal.
----
Potentiometer Input Error (Position-proportional Models Only)