EasyManua.ls Logo

Omron E5DC-RX0ASM-015 - User Manual

Omron E5DC-RX0ASM-015
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
1
New Product
Digital Temperature Controller
E5CC/E5EC/E5AC/E5DC
The new standard in temperature control is
higher in every respect
E5CC (48 × 48 mm) / E5EC (48 × 96 mm) / E5AC (96 × 96 mm)
E5DC (22.5 mm Wide, and DIN Track-mounting Type)
Large White PV Display That's Easier to Read.
Easy to Use, from Model Selection to Setup and Operation.
A Complete Range of I/O Capacities, Functions, and Performance.
Handles More Applications.
New Models That Mount to DIN Track and Are Ideal for HMI/PLC Connections.
48 × 48 mm
48 × 96 mm
E5CC
E5EC
96 × 96 mm
E5AC E5DC
22.5 mm Wide, and
DIN Track-mounting Type

Questions and Answers

  • D
    danielboyleSep 9, 2025
    How to set an end node for Omron Temperature Controller communication line?
    • K
      Karen ArcherSep 9, 2025
      If an end node has not been set at each end of the communications line on your Omron Temperature Controller, set or connect terminating resistance at each end of the line.
  • K
    Kendra MorganSep 7, 2025
    How long to wait before sending the next command to Omron E5DC-RX0ASM-015 Temperature Controller?
    • M
      Mr. Jeffrey JonesSep 8, 2025
      If the host device sent the next command too soon after receiving a response from the Controller, wait for at least 2 ms after receiving a response before sending the next command.
  • J
    jpetersenAug 22, 2025
    What to do if temperature error is large on Omron Controller (S.Err display)?
    • O
      ochoapamelaAug 22, 2025
      If you are seeing a large temperature error or an S.Err display on your Omron Controller, it may indicate an input type mismatch. Check the sensor type and reset the input type correctly.
  • P
    Patricia TrujilloSep 5, 2025
    What type of communication cable should I use for Omron E5DC-RX0ASM-015?
    • C
      Crystal McintoshSep 5, 2025
      If the wrong communications cable has been used for your Omron Temperature Controller, use shielded twisted-pair cable for the communications cable.
  • D
    Dorothy JacksonSep 4, 2025
    What is the maximum length of the communication cable for Omron Temperature Controller?
    • M
      Melissa LunaSep 4, 2025
      If the communications cable is too long for your Omron Temperature Controller, remember that the total cable length is 500 m maximum for RS-485 communications.
  • W
    William PrestonSep 2, 2025
    How to synchronize baud rate and communication method on Omron E5DC-RX0ASM-015?
    • J
      Julie CruzSep 2, 2025
      If the same baud rate and communications method are not being used by all of the Controllers, host devices, and other nodes on the same communications line, set the same values for the following on all nodes: baud rate, protocol, data length, stop bits, and parity.
  • C
    Cody TateSep 1, 2025
    What to do if the Omron E5DC-RX0ASM-015 communication cable is broken?
    • J
      Jillian SmithSep 1, 2025
      If the communications cable is broken on your Omron Temperature Controller, replace the cable.
  • J
    Joseph SmithAug 31, 2025
    Why is the communication indicator on my Omron E5DC-RX0ASM-015 Temperature Controller PLC not lit?
    • H
      Henry RussellAug 31, 2025
      If the communications indicator on the PLC is not lit, it could be due to several reasons: * The power supply is not turned ON to the E5@C Controller with communications unit number 0. * The wiring is not correct. * The communications settings are not the same between the PLC and the E5@C. * The E5@C was moved to the initial setting level (setting area 1). * Check the cycle time of the PLC. If it is longer than the value set for the Receive Data Wait Time parameter, change the set value of this parameter so that it is longer than the cycle time.
  • J
    Jeremiah NielsenAug 30, 2025
    What to do if the Omron Temperature Controller communication line is disconnected?
    • E
      Elizabeth ReynoldsAug 30, 2025
      If the communications line has become disconnected on your Omron Temperature Controller, connect the communications line securely and tighten the screws.
  • C
    Cheryl GarciaAug 28, 2025
    How to fix incorrect communications wiring on Omron E5DC-RX0ASM-015?
    • T
      Timothy ClarkAug 29, 2025
      If the communications wiring is not correct on your Omron Temperature Controller, correct the wiring.

Omron E5DC-RX0ASM-015 Specifications

General IconGeneral
TypeDigital Temperature Controller
ModelE5DC-RX0ASM-015
Display TypeLCD
Power Supply100 to 240 VAC
Mounting TypePanel Mount
CommunicationRS-485
Output TypeRelay
Auxiliary outputs2
Number of Control Outputs1
Ambient Operating Temperature-10 to 55 °C
Input TypeThermocouple, RTD
Control OutputRelay
Control MethodPID
Size48 x 96 mm
Ambient Operating Humidity25 to 85%RH