6   Parameters
6 - 36
E5@C Digital Temperature Controllers User’s Manual (H174)
oc-h
Open/Close Hysteresis A Position-proportional Model must be used.
• The Open/Close Hysteresis parameter is used to shift the ON and OFF points for the
open output and close output to prevent output chattering.
 Related Parameters
Position Proportional Dead Band (Adjustment Level): Page 6-35
sqrp
Extraction of Square Root Low-cut 
Point 
The input type must be an analog input, and the 
Extraction of Square Root Enable parameter must 
be set to ON.
• This parameter sets the extraction of square root low-cut point used for the inputs. The
data after extracting the square root is shown below.
• The low-cut point is used for extracting the square root for flowrate sensors.
 Related Parameters
Extraction of Square Root Enable (Initial Setting Level): Page 6-60
Setting
Setting range Unit Default
0.1 to 20.0 % 0.8
0
Argument 1 (input data)
Operation result
100% FS
100% FS
Extraction of square 
root low-cut point
Setting range Unit Default
0.0 to 100.0 % 0.0