6 - 49
6   Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-7  Initial Setting Level
6
 
3 Lower-limit Set the downward deviation 
in the set point by setting 
the alarm value (X). The 
alarm is ON when the PV is 
lower than the SP by the 
deviation or more.
4 Upper- and 
lower-limit range
*1
*3 Set the upward deviation in 
the set point for the alarm 
upper limit (H) and the 
lower deviation in the set 
point for the alarm lower 
limit (L). The alarm is ON 
when the PV is inside this 
deviation range.
5 Upper- and 
lower-limit with 
standby sequence
*1
*5
*4 A standby sequence is 
added to the upper- and 
lower-limit alarm (1). 
*6
6 Upper-limit with 
standby sequence
A standby sequence is 
added to the upper-limit 
alarm (2). 
*6
7 Lower-limit with 
standby sequence
A standby sequence is 
added to the lower-limit 
alarm (3). 
*6
8 Absolute-value 
upper-limit
The alarm will turn ON if the 
process value is larger than 
the alarm value (X) 
regardless of the set point. 
9 Absolute-value 
lower-limit
The alarm will turn ON if the 
process value is smaller 
than the alarm value (X) 
regardless of the set point. 
10 Absolute-value 
upper-limit with 
standby sequence
A standby sequence is 
added to the absolute-value 
upper-limit alarm (8). 
*6
11 Absolute-value 
lower-limit with 
standby sequence
A standby sequence is 
added to the absolute-value 
lower-limit alarm (9). 
*6
12 LBA (alarm 1 type 
only)
*7
13 PV change rate 
alarm
*8
14 SP absolute-value 
upper-limit alarm
This alarm type turns ON 
the alarm when the set 
point (SP) is higher than the 
alarm value (X).
15 SP absolute-value 
lower-limit alarm
This alarm type turns ON 
the alarm when the set 
point (SP) is smaller than 
the alarm value (X).
Set 
value
Alarm type
Alarm output operation
Description of function
When alarm value 
X is positive
When alarm value 
X is negative
ON
OFF
0
X
PV
ON
OFF
0
X
PV
ON
OFF
0
X
PV
ON
OFF
0
X
SP
ON
OFF
0
X
SP