2 - 33
2 Preparations
E5@C Digital Temperature Controllers User’s Manual (H174)
2-2 Using the Terminals
2
2-2-3 E5CC-B Terminal Block Wiring Example
Model Numbers
All E5CC-B models have universal sensor inputs, so the code in the model number is always “M.”
Terminal Details
Do not connect anything to the terminals that are shaded gray.
Precautions for Correct Use
When complying with EMC standards, the line connecting the sensor must be 30 m or less. If
the cable length exceeds 30 m, compliance with EMC standards will not be possible.
The sensor input is not electrically isolated from the internal circuits. If you use a grounded
thermocouple, do not connect one of the sensor input terminals to ground. (If the sensor input
terminals are connected to ground, errors will occur in the measured temperature as a result
of leakage current.)
Sensor Input
TC (thermocouple)
Pt (resistance
thermometer)
I (current) V (voltage)
E5CC-@@ @ @ B M-@@@
Sensor input
+
6
7
8
A
B
B
6
7
8
+
mA
6
7
8
+
V
6
7
8

Table of Contents

Other manuals for Omron E5GC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5GC and is the answer not in the manual?

Omron E5GC Specifications

General IconGeneral
BrandOmron
ModelE5GC
CategoryTemperature Controller
LanguageEnglish

Related product manuals