CompoWay/F Communications Procedures
• Software Reset
Command code 07 is used to start the processing that occurs when the power is turned ON.
A software reset can be performed in setup area 0 or 1. (There is no response to this com-
mand.)
• Move to Setup Area
Command code 08 is used to change the setup area under the following conditions. Changing
the setup area can be performed in setup area 0 or 1.
• Operation must be stopped to move from setup area 0 to 1.
• Moving from setup area 1 to 0 is possible at any time.
• Accumulated Operating Time Clear
Command code 09 is used to clear the Accumulated Operating Time of the motor to 0.0 (0 h).
The Accumulated Operating Time can be cleared only in setup area 1.
3.Response Code
Normal Completion
Error Completion
Response code Name Description
0000 Normal completion No errors were found.
Response code Error name Description
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1100 Parameter error The write data is out of the setting range.
2203 Operation error • A RUN/STOP command was sent in Initial Settings
Mode.
• A Parameter Initialization command was sent in RUN
Mode or Adjustment Mode.
• EEPROM error or initialization has not been per-
formed.
• A RUN/STOP command was output when the Opera-
tion Command Selection was set to use the PLC
(i.e., operation according to the STF/STR control
inputs).
• Reverse operation was specified even though
reverse operation is prohibited.