How to resolve BB (External Baseblock) error on Omron SYSDRIVE 3G3SV-B2002-E?
- TTiffany BrownSep 12, 2025
If your Omron Inverter displays the error code BB (External Baseblock), check the sequence circuit.

How to resolve BB (External Baseblock) error on Omron SYSDRIVE 3G3SV-B2002-E?
If your Omron Inverter displays the error code BB (External Baseblock), check the sequence circuit.
How to fix OV (Overvoltage) on Omron Inverter?
If your Omron Inverter displays an OV (Overvoltage) error, you can try increasing the deceleration time or connecting an optional braking resistor.
Why is my Omron Inverter overheating (OH error)?
If your Omron Inverter displays an OH (Inverter Overheat) error, it could be due to several reasons: * The load might be too large. * The V/f characteristics might not be proper. * The setting time might be too short. * The ambient temperature might exceed 45°C. To resolve this, correct the load size, V/f set value, or ambient temperature accordingly.
What causes UV (Undervoltage) error on Omron SYSDRIVE 3G3SV-B2002-E Inverter?
If your Omron Inverter displays an UV (Undervoltage) error, it could be due to: * Reduced input power supply voltage. * Open phases. * Momentary power loss. Check the power supply voltage, ensure the main circuit power supply wiring is properly connected, and verify that the terminal screws are tightened well.
How to troubleshoot OL1 (Motor Overload) on Omron Inverter?
If your Omron Inverter displays an OL1 (Motor Overload) error, the suggested solution is to correct the load size, adjust the operation pattern, or modify the V/f set value. Also, ensure you set the rated current value as described on the motor nameplate.
What should I do if my Omron SYSDRIVE 3G3SV-B2002-E shows OL2 (Inverter Overload) error?
If your Omron Inverter displays an OL2 (Inverter Overload) error, the suggested solution is to correct the load size, adjust the operation pattern, or modify the V/f set value. Additionally, recheck the inverter capacity to ensure it is adequate for the application.
How to resolve OL3 (Overtorque Detection) error on Omron Inverter?
If your Omron Inverter displays an OL3 (Overtorque Detection) error, check the machine using its status and remove the cause. Alternatively, increase the set value.
What to do if Omron SYSDRIVE 3G3SV-B2002-E displays CPF-07 (Thermistor fault)?
If your Omron Inverter displays the error code CPF-07 (Thermistor fault), the suggested solution is to replace the inverter.
What to do if Omron Inverter has no display (Fuse Blown)?
If your Omron Inverter shows no display and the fuse is blown, the suggested solution is to replace the inverter.
What to do for CPF-05 (AD converter fault) on Omron Inverter?
If your Omron Inverter displays the error code CPF-05 (AD converter fault), turn off the power supply and then turn it back on. If the fault persists, the suggested solution is to replace the inverter.
| Type | Inverter |
|---|---|
| Model | 3G3SV-B2002-E |
| Series | SYSDRIVE 3G3SV |
| Input Frequency | 50/60 Hz |
| Motor Capacity | 0.4 kW |
| Input Voltage | 200-240V AC |
| Output Voltage | 200-240 VAC |
| Output Frequency | 400 Hz |
| Cooling Method | Fan Cooled |
| Protection Features | Overcurrent, Overvoltage, Undervoltage, Overheat, Short Circuit |
| Ambient Temperature | -10°C to +50°C |
| Altitude | 1000 m |
| Vibration | 5.9 m/s2 |
| Storage Temperature | -20 to +60 °C (-4 to 140 °F) |
| Humidity | 5-95% (non-condensing) |
Identifies and illustrates the main components of the SYSDRIVE 3G3SV inverter.
Instructions for checking the inverter unit after unpacking and verifying part numbers.
Guidelines for proper installation location and environmental conditions for the inverter.
Detailed instructions for connecting the main circuit and control circuit wiring.
Procedures for checking the inverter before operation and methods for operating it.
Periodic inspection guidelines and corrective actions for maintaining the inverter unit.
Information on fault displays, their causes, and corrective actions for troubleshooting.
Technical specifications, including model numbers, electrical characteristics, and dimensions.
Describes two installation methods for the digital operator: hand operation and panel mounting.
Details the layout and functions of the digital operator's display and buttons.
Provides an overview of the main functions of the digital operator and the inverter.
Explains how to navigate and set functions and constants using the DRIVE and PRGM modes.
Illustrates a typical operation sequence using the digital operator.
Covers procedures for resetting constants to factory settings and restricting write-in access.
Details adjustments for frequency setting value, output frequency bias, and gain.
Explains how to monitor frequency reference, output frequency, current, and fault contents.
A comprehensive list of functions and constants with their initial settings and page references.
Detailed explanations of various functions and constants, including password and mode settings.
Outlines the inverter's protection functions, their explanations, and fault outputs.
Describes warning indicators and self-diagnosis features for inverter status.