Modular Temperature Controller EJ1 5
■ Input Ranges
Sensor inputs are fully multi-input. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be
selected.
Inputs can be set for each channel using multi-inputs.
Input type Platinum resistance
thermometer
Name Pt100 JPt100
Tem-
pera-
ture
range
(°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
−100.0
−200.0
850
500.0 500.0
100.0 100.0
0.0 0.0
−200 −199.9 −199.9
Setting number
01234
Input type Thermocouple ES1B Infrared
Thermosensor
Analog input
Name K J T E L U N R S B W PL
II
10
to
70
°C
60
to
120
°C
115
to
165
°C
140
to
260
°C
4 to
20
mA
0 to
20
mA
1 to
5 V
0 to
5 V
0 to
10 V
Tem-
pera-
ture
range
(°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
−100.0
−200.0
2300
Any of the following ranges,
by scaling:
−1999 to 9999
−199.9 to 999.9
−19.99 to 99.99
−1.999 to 9.999
1800
1700 1700
1300 1300 1300
850 850
600
500.0
400.0 400 400.0 400 400.0
260
120 165
90
100
0 00 000000
−20.0 −100 −20.0 −100
−200 −200 −199.9 −200 −199.9 −200
Setting number
5 6 7 8 9 1011121314151617181920212223242526272829
Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995, IEC584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
PL II: According to Platinel II Electromotive Force
Table by Engelhard Corp.
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997 IEC 751
Shaded ranges indicate default settings.