C-A-4 Contact Protection Circuits 
Using a contact protection circuit is effective in increasing contact 
durability and minimizing the production of carbides and nitric acid. 
The following table shows typical examples of contact protection 
circuits. Use them as guidelines for circuit design.
1. Depending on factors such as the nature of the load and the 
Relay characteristics, the effects may not occur at all or adverse 
effects may result. Therefore be sure to check operation under 
the actual load conditions.
2. When a contact protection circuit is used, it may cause the 
release time (breaking time) to be increased. Therefore be sure to 
check operation under the actual load conditions. 
Typical Examples of Contact Protection Circuits
Do not use the following types of contact protection circuit.
Note: Although it is thought that switching a DC inductive load is more difficult than a resistive load, an appropriate contact protection circuit can achieve almost the 
same characteristics.
C-A-5 Countermeasures for Surge from External 
Circuits
Install contact protection circuits, such as surge absorbers, at 
locations where there is a possibility of surges exceeding the Relay 
withstand voltage due to factors such as lightning. If a voltage 
exceeding the Relay withstand voltage value is applied, it will cause 
line and insulation deterioration between coils and contacts and 
between contacts of the same polarity. 
Circuit example Applicable 
current
Features and remarks Element selection
AC DC
CR
*See 
remarks.
(Yes)
Yes *Load impedance must be much smaller than 
the CR circuit impedance when using the Relay 
for an AC voltage.
When the contacts are open, current flows to the 
inductive load via CR. 
Use the following as guides for C and R values: 
C: 0.5 to 1 μF per 1 A of contact current (A) 
R: 0.5 to 1 
Ω per 1 V of contact voltage (V) 
These values depend on various factors, 
including the load characteristics and variations 
in characteristics. Confirm optimum values 
experimentally.
Capacitor C suppresses the discharge when the 
contacts are opened, while the resistor R limits 
the current applied when the contacts are closed 
the next time. 
Generally, use a capacitor with a dielectric 
strength of 200 to 300 V. For applications in an 
AC circuit, use an AC capacitor (with no polarity).
If there is any question about the ability to cut off 
arcing of the contacts in applications with high 
DC voltages, it may be more effective to connect 
the capacitor and resistor across the contacts, 
rather than across the load. Perform testing with 
the actual equipment to determine this.
Yes Yes The release time of the contacts will be 
increased if the load is a Relay or solenoid. 
Diode No  Yes The electromagnetic energy stored in the 
inductive load reaches the inductive load as 
current via the diode connected in parallel, and 
is dissipated as Joule heat by the resistance of 
the inductive load. This type of circuit increases 
the release time more than the CR type.
Use a diode having a reverse breakdown voltage 
of more than 10 times the circuit voltage, and a 
forward current rating greater than the load 
current. A diode having a reverse breakdown 
voltage two or three times that of the supply 
voltage can be used in an electronic circuit 
where the circuit voltage is not particularly high.
Diode + Zener 
diode
No Yes This circuit effectively shortens the release time 
in applications where the release time of a diode 
circuit is too slow.
The breakdown voltage of the Zener diode 
should be about the same as the supply voltage.
Varistor Yes Yes This circuit prevents a high voltage from being 
applied across the contacts by using the 
constant-voltage characteristic of a varistor. This 
circuit also somewhat increases the release 
time. Connecting the varistor across the load is 
effective when the supply voltage is 24 to 48 V, 
and across the contacts when the supply voltage 
is 100 to 240 V.
The cutoff voltage Vc must satisfy the following 
conditions. For AC, it must be multiplied by  . 
    Vc > (Supply voltage 
× 1.5)
If Vc is set too high, its effectiveness will be 
reduced because it will fail to cut off high 
voltages.
This circuit arrangement is very effective for diminishing 
arcing at the contacts when breaking the circuit. However, 
since electrical energy is stored in C (capacitor) when the 
contacts are open, the current from C flows into the 
contacts when they close. This may lead to contact 
welding.
This circuit arrangement is very useful for diminishing 
arcing at the contacts when breaking the circuit. However, 
since the charging current to C flows into the contacts 
when they are closed, contact welding may occur.
Power
supply
(See
remarks.)
CR
Inductive
load
(See
remarks.)
C
R
Power
supply
Inductive
load
Power
supply
Inductive
load
Inductive
load
Power
supply
Inductive
load
Power
supply
2
LoadPower
supply
C
LoadPower
supply
C
http://www.ia.omron.com/
C-6
(c)Copyright OMRON Corporation 2007   All Rights Reserved. 
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com