C-B-4 Applied Voltage Waveform for Input Voltage
As a rule, power supply waveforms are based on the rectangular 
(square) waveforms, and do not operate in such a way that the 
voltage applied to the coil slowly rises and falls. Also, do not use 
them to detect voltage or current limit values (i.e., using them for 
turning ON or OFF at the moment a voltage or current limit is 
reached).
This kind of circuit causes faulty sequence operations. For example, 
the simultaneous operability of contacts may not be dependable (for 
multi-pole Relays, time variations must occur in contact operations), 
and the must-operate voltage varies with each operation. In addition, 
the operation and release times are lengthened, causing durability to 
drop and contact welding. Be sure to use an instantaneous ON/OFF.
-B-5 Preventing Surges when the Coil Is Turned OFF
Counter electromotive force generated from a coil when the coil is 
turned OFF causes damage to semiconductor elements and faulty 
operation.
As a countermeasure, install surge absorbing circuits at both ends of 
the coil. When surge absorbing circuits have been installed, the 
Relay release time will be lengthened, so be sure to check operation 
using the actual circuits.
External surges must be taken into account for the repetitive peak 
reverse voltage and the DC reverse voltage, and a diode with 
sufficient capacity used. Also, ensure that the diode has an average 
rectified current that is greater than the coil current.
Do not use under conditions in which a surge is included in the power 
supply, such as when an inductive load is connected in parallel to the 
coil. Doing so will cause damage to the installed (or built-in) coil 
surge absorbing diode.
C-B-6 Leakage Current to Relay Coils
Do not allow leakage current to flow to Relay coils. Construct a 
corrective circuit as shown in examples 1 and 2 below.
Example: Circuit with Leakage Current Occurring
Corrective Example 1
Corrective Example 2: 
When an Output Value Is Required in the Same Phase as the 
Input Value
C-B-7 Using with Infrequent Switching
For operations using a microload and infrequent switching, 
periodically perform continuity tests on the contacts. When switching 
is not executed for contacts for long periods of time, it causes contact 
instability due to factors such as the formation of film on contact 
surfaces. The frequency with which the inspections are needed will 
depend on factors such as the operating environment and the type of 
load.
-B-8 Configuring Sequence Circuits
When configuring a sequence circuit, care must be taken to ensure 
that abnormal operation does not occur due to faults such as sneak 
current. 
The following diagram shows an example of sneak current. After 
contacts A, B, and C are closed causing Relays X
1, X2, and X3 to 
operate, and then contacts B and C are opened, a series circuit is 
created from A to X
1 to X2 to X3. This causes the Relay to hum or to 
not release.
The following diagram shows an example of a circuit that corrects the 
above problem. Also, in a DC circuit, the sneak current can be 
prevented by means of a diode.
C-B-9 Connecting Relay Grounds
Do not connect a ground when using a Relay at high temperatures or 
high humidity. Depending on the grounding method, electrolytic 
corrosion may occur, causing the wire to the coil to sever. If the Relay 
must be grounded, use the method shown in the following diagrams.
(1) Ground the positive side of the power supply. (Fig. 1 and Fig. 2)
(2) If grounding the positive side of the power supply is not possible 
and the negative side must be grounded, connect a switch at the 
positive side so that the coil is connected to the negative side. 
(Fig. 3)
(3) Do not ground the negative side and connect a switch to the 
negative side. This will cause electrolytic corrosion to occur. (Fig. 
4)
C-B-10 Individual Specifications for Must-operate/
release Voltages and Operate/Release Times
If it is necessary to know the individual specifications of 
characteristics, such as must-operate voltages, must-release 
voltages, operate times, and release times, please contact your 
OMRON representative.
TE
I
O
Incorrect
Correct
Correct
X1
A
C
B
X
2 X3
Incorrect
X1
C
A
B
D
X
2 X3
Correct
CoreCore
CoreCore
Fig. 1
Fi
. 3
Fig. 2
Fi
. 4
Difference in electric potential
Correct
Incorrect
Correct
Correct
http://www.ia.omron.com/
C-8
(c)Copyright OMRON Corporation 2007   All Rights Reserved. 
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com