3 Error Tables
3-20
NJ-series Troubleshooting Manual (W503)
54011409 hex That File Name
Already Exists
An instruction could not be
executed because the file
name specified for the
instruction already exists.
A file already exists
with the same name
as the name specified
for the instruction to
create.
S NJ-series
Instruc-
tions Ref-
erence
Manual
(Cat. No.
W502)
5401140A hex Write Access
Denied
An attempt was made to
write to a write-protected
file or directory when an
instruction was executed.
The file or directory
specified for the
instruction to write is
write-protected.
S Same as
above.
5401140B hex Too Many Files
Open
The maximum number of
open files was exceeded
when opening a file for an
instruction.
The maximum number
of open files was
exceeded when open-
ing a file for an instruc-
tion.
S Same as
above.
5401140C hex Directory Does Not
Exist
The directory specified for
an instruction does not
exist.
The directory speci-
fied for an instruction
does not exist.
S Same as
above.
5401140D hex File or Directory
Name Is Too Long
The file name or directory
name that was specified for
an instruction is too long.
The file name or direc-
tory name that was
specified for the
instruction to create is
too long.
S Same as
above.
5401140E hex SD Memory Card
Access Failed
SD Memory Card access
failed.
The SD Memory Card
is broken.
The SD Memory Card
slot is broken.
S Same as
above.
54011800 hex EtherCAT Commu-
nications Error
Accessing the EtherCAT
network failed when an
instruction was executed.
The EtherCAT network
is not in a usable sta-
tus.
S Same as
above.
54011801 hex EtherCAT Slave
Does Not Respond
Accessing the target slave
failed when an instruction
was executed.
The target slave does
not exist.
The target slave is not
in an operating condi-
tion.
S Same as
above.
54011802 hex EtherCAT Timeout A timeout occurred while
trying to access an Ether-
CAT slave when an instruc-
tion was executed.
Comm
unications with
the target slave timed
out.
S
Same as
above.
54011803 hex Reception Buffer
Overflow
The receive data from an
EtherCAT slave overflowed
the receive buffer when an
instruction was executed.
The receive data from
the slave overflowed
the receive buffer.
S Same as
above.
54011804 hex SDO Abort Error An SDO abort error was
received from an EtherCAT
slave when an instruction
was executed.
Depends on the speci-
fications of the slave.
S Same as
above.
54011805 hex Saving Packet
Monitor File
An instruction for packet
monitoring was executed
while saving an EtherCAT
packet monitor file.
An instruction for
packet monitoring was
executed while saving
an EtherCAT packet
monitor file.
S Same as
above.
54011806 hex Packet Monitoring
Function Not
Started
A Stop EtherCAT Packet
Monitor instruction was
executed when EtherCAT
packet monitoring was
stopped.
A Stop EtherCAT
Packet Monitor
instruction was exe-
cuted when EtherCAT
packet monitoring was
stopped.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Refer-
ence
Maj Prt Min Obs Info

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB
Safety FunctionOptional
Storage Temperature-20°C to 75°C
Communication PortsUSB
DimensionsVaries by model
WeightVaries by model