7IO-Link Connection Procedure
28
12
Check that the following LED
indicators on Slave Terminal
show the communication ready
status.
RUN: Not lit
ERR: Not lit
TS: Green flashing
L/A IN: Green flickering
L/A OUT: Not lit
13
The LED indicators on
Controller are as shown below
when an error occurs in
EtherCAT communications due
to the temporary interruption of
Unit power supply to Slave
Terminal.
NET RUN: Not lit
NET ERR: Red flashing
LINK/ACT: Yellow flashing
*The NJ-series Controllers also
have the same LED indicator
status.
14
Select Troubleshooting from
the Tools Menu.
15
The Troubleshooting Dialog Box
is displayed. Check that a Link
OFF Error occurs as shown in
the figure on the right.
Click Reset All.
16
The dialog box on the right is
displayed. Check the contents
and click Yes.
Built-in EtherCAT (Port 3)
Status Indicators