S8VK-S
11
240 W (S8VK-S24024) Horizontal separation: 15 mm or more
Note: 1. At less than 90 VAC, derate the load at 2.5%/V.
2. For a DC input, reduce the load given in the above derating
curve by multiplying by the following coefficients.
S8VK-S24024: 0.8
Standard mounting, mounted with Front-mounting Bracket
480 W (S8VK-S48024) Horizontal separation: 15 mm or more
Note: 1. At less than 100 VAC, derate the load at 1%/V.
2. For a DC input, reduce the load given in the above derating
curve by multiplying by the following coefficients.
S8VK-S48024: 0.8
Standard mounting, mounted with Front-mounting Bracket
240 W (S8VK-S24024):
Front, side-by-side mounting
Horizontal separation: Less than 15 mm
Note: 1. Apply the rated voltage
Front, Side-by-side mounting
480 W (S8VK-S48024)
: Front, side-by-side mounting
Horizontal separation: Less than 15 mm
Note: 1. Apply the rated voltage
Front, Side-by-side mounting
0 500
1,000 1,500 2,000 2,500 3,000 3,500
120
100
80
87
75
60
40
20
0
55°C max
60°C
65°C
70°C
100%
90%
77%
65%
Load ratio (%)
Altitude (m)
0 500
1,000 1,500 2,000 2,500 3,000 3,500
120
100
80
87
75
60
40
20
0
55°C max
60°C
65°C
70°C
100%
90%
77%
65%
Load ratio (%)
Altitude (m)
120
100
80
60
40
20
0
0 500
1,000 1,500 2,000 2,500 3,000 3,500
100%
85%
75%
35°C max
40°C
55°C
Load ratio (%)
Altitude (m)
120
100
80
60
40
20
0
0 500
1,000 1,500 2,000 2,500 3,000 3,500
100%
85%
75%
35°C max
40°C
55°C
Load ratio (%)
Altitude (m)