EasyManua.ls Logo

Omron SYSDRIVE 3G3FV-*-CUE - Page 34

Omron SYSDRIVE 3G3FV-*-CUE
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.dadehpardazan.ir 88594014-15
2-15
Symbol Signal levelFunctionName
Se-
quence
9 Multi-function contact output (NO con-
dition)
Set by parameter H2-01 (during running). Contact output
(SPST-NO)
output
10 Multi-function contact output common
30 VDC, 1 A max.
250 VAC, 1 A max.
25 Multi-function output 1
Set by parameter H2-02 (zero speed Open collector out-
27 Multi-function output 1 common
detection). put
26 Multi-function output 2
Set by parameter H2-03 (agree output ref-
48 V, 50 mA max.
37 Multi-function output 2 common
erence detection).
18 Fault output (NO condition)
When fault occurs: Contact output
19 Fault output (NC condition)
Terminals 18 to 20: Closed
(SPDT)
20 Fault output common
Terminals 19 to 20: Open
30 VDC, 1 A max.
250 VAC, 1 A max.
Analog
output
21 Multi-function analog output 1 Set by parameter H4-01. (Output frequen-
cy: 0 to ±10 V/±100% frequency)
0 to ±10 VDC, 0 to
10 VDC, 2 mA
23 Multi-function analog output 2 Set by parameter H4-01. (Output current:
5 V/Inverter rated current)
max.
22 Multi-function analog output common Common for analog output.
---
40
For option
41
42
43
Note Multi-function inputs 1 to 5, multi-function contact outputs, and multi-function output 1 to 2 allow
selection of various functions by changing parameter settings. The settings shown in paren-
theses in the Function column for the multi-function inputs and multi-function contact outputs indi-
cate the default settings.
H 3G3HV Series
D Terminal Block Configuration (400-V Class with 3.7-kW Output, CUE Models)
Control
circuit
terminals
Main circuit
terminals
Installation Chapter 2

Related product manuals