3-6SectionOffset and Gain Adjustment
56
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 00 (the Offset Bit) of IR word n+1. (Hold the ON status.)
CLR
00000
SHIFT
CONT
#
1
B
0
A
1
B
0
A
0
A
MONTR
10100
^OFF
PLAY
SET
10100
ON
2. Check whether the output devices are connected.
A0
A1
A2
A3
A0
A1
A2
A3
Voltage output
Current output
Output 1
Output 1
3. Monitor IR word n+8 and check the set value while the Offset Bit is ON.
CLR
00000
SHIFT
CH
*
1
B
0
A
8
MONTR
c108
0000
4. Change the set value so that the output voltage and output current are as
shown in the following table. The data can be set within the indicated
ranges.
Output signal range Output voltage/current Output range
0 to 10 V 0 V
FF38 to 00C8
–10 to 10 V 0 V
1 to 5 V 1 V
4 to 20 mA 4 mA