TURBINE FLOW METER
Installation and Operation Guide
05-13
0721-1 / 13518

Questions and Answers

  • D
    David DennisJul 28, 2025
    How to troubleshoot no signal on Onicon F-1100?
    • J
      james83Jul 28, 2025
      To troubleshoot a 'no signal' issue with your Onicon Measuring Instruments, start by verifying that the meter is inserted correctly into the pipe and that the electronics enclosure is parallel with the pipe. Next, check the 24 V supply voltage and ensure correct wiring to the control system, referring to the wiring diagram. Finally, inspect the turbines for any debris.
  • D
    deborah92Aug 5, 2025
    What to do if analog signal is incorrect on Onicon F-1100?
    • S
      Stacey PittmanAug 5, 2025
      If the analog signal on your Onicon Measuring Instruments seems high or low and does not correspond to the frequency output, check for a ground loop or offset voltage. Disconnect the analog signal input to the control system and measure the analog outputs directly from the flow meter. Re-connect the signal input to the control system and measure the analog signals again. Any difference between these readings indicates a potential ground loop or offset voltage.
  • E
    Eric BrooksAug 11, 2025
    Why is the reading too high on my Onicon Measuring Instruments?
    • W
      williamcruzAug 11, 2025
      If the reading on your Onicon Measuring Instruments is too high, it could be due to several factors. First, ensure there is adequate straight pipe run upstream of the meter. Verify the pipe size and contact the factory if it differs from the calibration tag. Also, check that the meter is inserted correctly into the pipe and that the electronics enclosure is parallel with the pipe. Confirm the wiring to the control system is correct and that output signals agree. Ensure the control system is programmed for the correct flow range or scale factor, and inspect the turbines for debris.
  • T
    Tyler RichardsonAug 19, 2025
    Why no flow rate on Onicon display module, but control system displays it?
    • A
      Angela LoweAug 19, 2025
      If your control system displays the flow rate, but there is no flow rate indication on the local display module or BTU Meter for your Onicon Measuring Instruments, verify that all wires from the flow meter were connected to the display module or BTU meter. Specifically, ensure that the frequency output wire (green) is connected, as it is essential for any ONICON display or BTU meter to function correctly.

Summary

Safety Information

General Safety Precautions

General safety precautions to observe during installation, operation, and repair.

Understanding Warning Symbols

Explanation of symbols like WARNING, CAUTION, and IMPORTANT NOTE.

Introduction to Turbine Flow Meters

Purpose of the Turbine Flow Meter Guide

Provides specific information for installation, operation, and maintenance of turbine flow meters.

Typical Turbine Flow Meter Operation

Explains how turbine meters measure fluid velocity using turbine rotation and frequency.

Standard Features and Specifications

Details accuracy, sensing methods, pipe sizes, temperature, pressure, and materials.

Model Numbering and Warranty Information

Explains meter model codes, serial numbers, and warranty details.

Installation Site and Preparation

Unpacking and Component Verification

Ensures all documentation and meter parts are present and undamaged.

Site Selection Criteria

Guidance on choosing accessible locations with adequate straight pipe runs.

Insertion Meter Straight Run Requirements

Specifies minimum straight pipe lengths for F-1100, F-1200, FB-1200 series.

Inline Meter Straight Run Requirements

Specifies minimum straight pipe lengths for inline meters.

Meter Mechanical Installation Procedures

Insertion Meter Mechanical Installation

Details installing the meter through an isolation valve assembly.

Installing the Insertion Meter

Procedure for inserting the meter using a depth gauge or manual method.

Removing the Insertion Meter

Step-by-step process for safe removal of the meter under pressure.

Wiring and Start-up Procedures

Wiring Connections for Flow Meters

Instructions for connecting the flow meter's output signals to display or control systems.

Start-up and Commissioning Tips

Helpful hints for ensuring proper meter setup and calibration.

Insertion Meter Start-up and Commissioning

Step-by-step guide for verifying insertion meter installation and output signals.

Inline Meter Start-up and Commissioning

Steps for verifying inline meter installation and output signals.

Troubleshooting Common Flow Meter Issues

Solutions for problems like no signal, incorrect readings, or wiring errors.

Analog Adjustment Procedure

General Discussion of Analog Outputs

Explains analog output calibration and when adjustments might be needed.

Procedure for Analog Output Rescaling

Detailed steps for recalibrating analog output signals using test equipment.

Appendices

Appendix A: Wiring Diagrams

Diagrams showing user connections and internal wiring for various meter models.

Appendix B: Installation Hardware Instructions

Guides for installing specific hardware kits for different pipe types and methods.

Appendix C: Turbine Assembly Detail Drawings

Diagrams illustrating the assembly and maintenance of turbine rotors and bearings.

Appendix D: Conditions of Sale

Details ONICON's warranty, delivery, pricing, and legal terms for product sales.

Onicon F-1100 Series Specifications

General IconGeneral
BrandOnicon
ModelF-1100 Series
CategoryMeasuring Instruments
LanguageEnglish