TURBINE FLOW METER
Installation and Operation Guide
05-13
0721-1 / 13518

Other manuals for Onicon F-1210

Questions and Answers

  • J
    Johnny CisnerosAug 12, 2025
    How to troubleshoot no signal on Onicon F-1210?
    • A
      Alexis TannerAug 12, 2025
      To troubleshoot a 'no signal' issue with your Onicon Measuring Instruments, start by verifying that the meter is inserted correctly into the pipe and that the electronics enclosure is parallel with the pipe. Next, check the 24 V supply voltage and ensure correct wiring to the control system, referring to the wiring diagram. Finally, inspect the turbines for any debris.
  • T
    Tyler MercadoAug 15, 2025
    What to do if analog signal is incorrect on Onicon Measuring Instruments?
    • D
      dsmithAug 15, 2025
      If the analog signal on your Onicon Measuring Instruments seems high or low and does not correspond to the frequency output, check for a ground loop or offset voltage. Disconnect the analog signal input to the control system and measure the analog outputs directly from the flow meter. Re-connect the signal input to the control system and measure the analog signals again. Any difference between these readings indicates a potential ground loop or offset voltage.
  • P
    Paul WalkerAug 19, 2025
    Why is the reading too high or too low on my Onicon F-1210 Measuring Instruments?
    • P
      Paul PierceAug 19, 2025
      If the reading on your Onicon Measuring Instruments is too high or too low, start by verifying the pipe size. If the pipe size differs from what's on the calibration tag, contact the factory. Also, ensure the meter is correctly inserted into the pipe and that the electronics enclosure is parallel with the pipe. Check the wiring to the control system, confirm that the output signals are consistent, and that the control system is programmed for the correct flow range or scale factor. Lastly, inspect the turbines for any debris.
  • L
    Linda MirandaAug 23, 2025
    What to do if there is no signal from Onicon Measuring Instruments?
    • L
      Loretta StewartAug 23, 2025
      If your Onicon Measuring Instruments are showing no signal, first ensure that the meter is correctly inserted into the pipe and that the electronics enclosure is parallel with the pipe. Verify that the 24 V supply voltage is present and that the wiring to the control system is correct. Finally, check the turbines for any debris that may be obstructing the signal.
  • M
    michaeltorresAug 27, 2025
    Why doesn't the analog signal correspond to the frequency output in Onicon F-1210?
    • J
      Jessica TurnerAug 27, 2025
      If the analog signal on your Onicon Measuring Instruments seems high or low and doesn't match the frequency output, it might be due to a ground loop or offset voltage. To check, disconnect the analog signal input to the control system and measure the analog outputs directly from the flow meter. Then, reconnect the signal input to the control system and measure the analog signals again. Any difference between these readings indicates a potential ground loop or offset voltage. For further assistance, please contact ONICON.
  • J
    Janet FordAug 30, 2025
    How to fix no flow rate indication on the local display module of Onicon Measuring Instruments?
    • C
      Chelsea WalkerAug 31, 2025
      If your control system displays the flow rate, but there's no flow rate indication on the local display module or BTU Meter for your Onicon Measuring Instruments, verify that all wires from the flow meter are connected to the display module or BTU Meter. Specifically, the frequency output wire (green) must be connected for any ONICON Display or BTU Meter to function correctly.
  • C
    Catherine CooperSep 3, 2025
    Why is the reading too high on my Onicon F-1210 Measuring Instruments?
    • M
      Melissa DuranSep 3, 2025
      If the reading on your Onicon Measuring Instruments is too high, it could be due to several factors. First, ensure there is adequate straight pipe run upstream of the meter. Verify the pipe size and contact the factory if it differs from the calibration tag. Also, check that the meter is inserted correctly into the pipe and that the electronics enclosure is parallel with the pipe. Confirm the wiring to the control system is correct and that output signals agree. Ensure the control system is programmed for the correct flow range or scale factor, and inspect the turbines for debris.
  • C
    Cheyenne AndersonSep 7, 2025
    Why no flow rate on Onicon display module, but control system displays it?
    • B
      Bruce SolisSep 7, 2025
      If your control system displays the flow rate, but there is no flow rate indication on the local display module or BTU Meter for your Onicon Measuring Instruments, verify that all wires from the flow meter were connected to the display module or BTU meter. Specifically, ensure that the frequency output wire (green) is connected, as it is essential for any ONICON display or BTU meter to function correctly.

Summary

SAFETY INFORMATION

SECTION 2.0: UNPACKING

SECTION 3.0: INSTALLATION, REMOVAL & ADJUSTMENT

Insertion Meter Mechanical Installation

Details the mechanical aspects of installing insertion turbine flow meters.

Installing the Insertion Meter

Step-by-step instructions for the physical installation of the insertion meter.

REMOVAL OF THE INSERTION METER

INLINE METER STRAIGHT RUN REQUIREMENTS AND MECHANICAL INSTALLATION

WIRING CONNECTIONS

SECTION 4.0: STARTUP & COMMISSIONING

Insertion Meter Start-up and Commissioning

Detailed procedure for starting up and commissioning insertion turbine meters.

Inline Meter Start-up and Commissioning

Detailed procedure for starting up and commissioning inline turbine meters.

Troubleshooting Guide

Lists common problems and their potential solutions for turbine flow meters.

SECTION 5.0: ANALOG ADJUSTMENT PROCEDURE

APPENDIX A

User Connections and Internal Wiring Diagrams

Provides diagrams for meter connections and internal wiring.

APPENDIX B

APPENDIX C

Onicon F-1210 Specifications

General IconGeneral
ModelF-1210
CategoryMeasuring Instruments
TypeElectromagnetic Flow Meter
InstallationInline
Output4-20 mA, Pulse
Power Supply12-30 VDC
Operating Temperature-4 to 140°F (-20 to 60°C)
Material316 Stainless Steel
Output Signal4-20 mA, pulse
Power12-30 VDC
Sizes1/2" to 72"
Accuracy±0.5% of reading