TURBINE FLOW METER
Installation and Operation Guide
05-13
0721-1 / 13518

Other manuals for Onicon F-1110

Questions and Answers

  • C
    Cynthia BurkeAug 14, 2025
    How to troubleshoot no signal on Onicon Measuring Instruments?
    • J
      Jill Herrera MDAug 14, 2025
      To troubleshoot a 'no signal' issue with your Onicon Measuring Instruments, start by verifying that the meter is inserted correctly into the pipe and that the electronics enclosure is parallel with the pipe. Next, check the 24 V supply voltage and ensure correct wiring to the control system, referring to the wiring diagram. Finally, inspect the turbines for any debris.
  • Z
    zavalarileyAug 17, 2025
    What to do if analog signal is incorrect on Onicon Measuring Instruments?
    • C
      Corey HardinAug 17, 2025
      If the analog signal on your Onicon Measuring Instruments seems high or low and does not correspond to the frequency output, check for a ground loop or offset voltage. Disconnect the analog signal input to the control system and measure the analog outputs directly from the flow meter. Re-connect the signal input to the control system and measure the analog signals again. Any difference between these readings indicates a potential ground loop or offset voltage.
  • D
    Dustin ClarkAug 21, 2025
    Why is the reading too high or too low on my Onicon F-1110?
    • W
      William HensonAug 21, 2025
      If the reading on your Onicon Measuring Instruments is too high or too low, start by verifying the pipe size. If the pipe size differs from what's on the calibration tag, contact the factory. Also, ensure the meter is correctly inserted into the pipe and that the electronics enclosure is parallel with the pipe. Check the wiring to the control system, confirm that the output signals are consistent, and that the control system is programmed for the correct flow range or scale factor. Lastly, inspect the turbines for any debris.
  • J
    joshuasalazarAug 25, 2025
    What to do if there is no signal from Onicon F-1110?
    • D
      Derek JonesAug 26, 2025
      If your Onicon Measuring Instruments are showing no signal, first ensure that the meter is correctly inserted into the pipe and that the electronics enclosure is parallel with the pipe. Verify that the 24 V supply voltage is present and that the wiring to the control system is correct. Finally, check the turbines for any debris that may be obstructing the signal.
  • R
    Rhonda DanielsAug 28, 2025
    Why doesn't the analog signal correspond to the frequency output in Onicon F-1110 Measuring Instruments?
    • G
      Gary ShahAug 28, 2025
      If the analog signal on your Onicon Measuring Instruments seems high or low and doesn't match the frequency output, it might be due to a ground loop or offset voltage. To check, disconnect the analog signal input to the control system and measure the analog outputs directly from the flow meter. Then, reconnect the signal input to the control system and measure the analog signals again. Any difference between these readings indicates a potential ground loop or offset voltage. For further assistance, please contact ONICON.
  • M
    Mike JuarezSep 1, 2025
    How to fix no flow rate indication on the local display module of Onicon Measuring Instruments?
    • M
      Michael SuttonSep 1, 2025
      If your control system displays the flow rate, but there's no flow rate indication on the local display module or BTU Meter for your Onicon Measuring Instruments, verify that all wires from the flow meter are connected to the display module or BTU Meter. Specifically, the frequency output wire (green) must be connected for any ONICON Display or BTU Meter to function correctly.
  • J
    Jason NorrisSep 4, 2025
    Why is the reading too high on my Onicon Measuring Instruments?
    • B
      briantaylorSep 5, 2025
      If the reading on your Onicon Measuring Instruments is too high, it could be due to several factors. First, ensure there is adequate straight pipe run upstream of the meter. Verify the pipe size and contact the factory if it differs from the calibration tag. Also, check that the meter is inserted correctly into the pipe and that the electronics enclosure is parallel with the pipe. Confirm the wiring to the control system is correct and that output signals agree. Ensure the control system is programmed for the correct flow range or scale factor, and inspect the turbines for debris.
  • J
    jerry28Sep 9, 2025
    Why no flow rate on Onicon display module, but control system displays it?
    • M
      Matthew RogersSep 9, 2025
      If your control system displays the flow rate, but there is no flow rate indication on the local display module or BTU Meter for your Onicon Measuring Instruments, verify that all wires from the flow meter were connected to the display module or BTU meter. Specifically, ensure that the frequency output wire (green) is connected, as it is essential for any ONICON display or BTU meter to function correctly.

Summary

Safety Information

Safety Precautions

General safety measures to be observed during installation, operation, service, and repair of the product.

Introduction to Turbine Flow Meters

Standard Features and Specifications

Details the technical specifications, accuracy, sensing methods, pipe sizes, and materials for the flow meters.

Installation, Removal, and Adjustment

Installation Site Selection Guidelines

Guidelines for choosing an appropriate location for meter installation, considering accessibility and pipe conditions.

Wiring Connections

Guides on making electrical connections between the flow meter and external systems, including cautions.

Startup and Commissioning

Helpful Hints for Start-up and Commissioning

Provides pre-commissioning tips and checks for ONICON turbine flow meters.

Insertion Meter Start-up and Commissioning

Step-by-step procedure for starting up and commissioning insertion turbine flow meters.

Inline Meter Start-up and Commissioning

Step-by-step procedure for starting up and commissioning inline turbine flow meters.

Troubleshooting Guide

Lists common problems and their possible solutions for ONICON turbine flow meters.

Analog Adjustment Procedure

Appendix A: Wiring Diagrams

Flow Meter Wiring Information

User Connections for Frequency Output Models

Wiring details for models with frequency output, showing connections to ONICON displays or BTU meters.

User Connections for Non-Isolated Analog Output Models

Wiring information for models with non-isolated analog outputs, detailing connections to control systems.

User Connections for Isolated Analog Output Models

Wiring information for models with isolated analog outputs, detailing connections to control systems.

User Connections for Divided Output Models

Wiring details for models with divided output, explaining connections for binary digital input.

User Connections for Scaled Output Models

Wiring details for models with scaled output, explaining connections for binary digital input.

Appendix B: Installation Hardware Instructions

Onicon F-1110 Specifications

General IconGeneral
BrandOnicon
ModelF-1110
CategoryMeasuring Instruments