EasyManuals Logo

Onicon F-1110 User Manual

Default Icon
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
Turbine Flow Meter Manual 05/13 - 0721-1 / 13518 Page 26
4.6 TROUBLESHOOTING GUIDE
NOTE: Also refer to the START-UP and COMMISSIONING GUIDE located on the preceding
pages.
REPORTED PROBLEM POSSIBLE SOLUTIONS
No signal
Verify that meter is inserted correctly into the pipe.
Verify that the electronics enclosure is parallel with the pipe.
Verify 24 V supply voltage.
Verify correct wiring to control system (see wiring diagram).
Check turbine(s) for debris.
Reading is too high or too low
Conrm that there is adequate straight pipe run upstream of the
meter. Verify pipe size. Contact factory if pipe size is different
from calibration tag.
Verify that meter is inserted correctly into the pipe.
Verify that the electronics enclosure is parallel with the pipe.
Verify correct wiring to control system (see wiring diagram).
Conrm that output signals agree with each other (frequency vs.
analog, etc.)
Conrm that control system is programmed for correct ow range
or scale factor.
Check turbine(s) for debris.
Analog signal seems high or
low and does not correspond
to frequency output
Check for ground loop or offset voltage:
Disconnect analog signal input to control system and measure
analog outputs directly from the ow meter.
Re-connect signal input to control system and measure the analog
signals again.
Any difference between these readings indicates a potential
ground loop or offset voltage.
Please contact ONICON for further assistance.
Control system displays ow
rate, but no ow rate
indication on local display
module or BTU Meter
Verify that all wires from ow meter were connected to the
display module or BTU meter.
The frequency output wire (green) must be connected for any
ONICON display or BTU meter.
For technical assistance, contact ONICON at (727) 447-6140.

Other manuals for Onicon F-1110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Onicon F-1110 and is the answer not in the manual?

Onicon F-1110 Specifications

General IconGeneral
BrandOnicon
ModelF-1110
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals