26
12. Determination of Storage Tank Size
Calculation of the smallest tank size:
Vsp = 15 Tb x Qn (1-0.3 x (QH/Qmin))
where: Vsp ….. volume of storage tank in l
Tb ...…. burning time in hours
Qn …… nominal heat capacity in kW
QH …… heat load of the buildings in kW
Qmin … lowest heat capacity in kW
The dimensions of the storage tank must be determined depending on the capacity, fuel
used, depending on which one has the biggest storage tank. No storage tank is needed if
the as calculated volume is less than 300l.